Control Description: The Zone Expansion Manager 325 is designed to simplify the wiring between tN4 thermostats and zone valves. The 325 has an internal transformer that supplies power to the tekmarNet+4 (tN4) thermostats and connected zone valves. Control + Microprocessor PID control; This is not a safety (limit) control Packaged Weight + 2.95 lb. (1338 g) Dimensions + 3-5/8" H x 5-3/8" W x 9/16" D (92 x 137 x 14 mm) Approvals + CSA C US, CSA/UL 61010-1, meets Class B: ICES and FCC Part 15 Ambient Conditions + Indoor use only, 32 to 122+F (0 to 50+C) ; RH equal to or less than 80% to 88+F (31+C), down to 50% from 104 to 122+F (40 to 50+C) ; Altitude <2000 m, Installation Category II, Pollution Category 2 Power Supply + Provided by interconnected Zone Manager Transformer + 24 V (ac) 8 VA Maximum Zone Group Pump C Relay + 0-10 V Minimum 2500 Ω Combined Relay Load + 115 V (ac) 5 A 1/4 hp, pilot duty 240 VA
Manuals
| # | Title | Languages | Pages | Updated |
|---|---|---|---|---|
| 1 | Install Instructions | EN | 4 | 2022-03-24 |
| 2 | Job Record | EN | 2 | 2022-11-22 |
| 3 | Submittal Sheet | EN | 2 | 2022-03-24 |
| 4 | Wiring Brochure | EN | 12 | 2022-11-22 |
| 5 | Zoning Solutions Brochure | EN | 12 | 2022-11-22 |