Square D TeSys U Motor Starter Non-Reversing Power Base (12A, 3P)

LUB12

Categories

Description

TeSys U Motor Starter Non-Reversing Power Base (12A) Specifications: Range: TeSys Product Name: TeSys U Product or Component Type: Non-Reversing Power Base Device Application: Motor Poles Description: 3P Suitability for Isolation: Yes [Ith] Conventional Free Air Thermal Current: 12 A Utilisation Category: AC-44, AC-43, AC-41 [Uc] Control Circuit Voltage: 24 V AC 50/60 Hz, 24 V DC, 48 V AC 50/60 Hz, 48...72 V DC, 110...220 V DC, 110...240 V AC 50/60 Hz Auxiliary Contact Composition: 1 NO + 1 NC Auxiliary Contacts Type: Linked Contacts 1 NO + 1 NC) IEC 60947-4-1, Mirror Contact 1 NC) State of the Power Draft IEC 60947-1 [Ue] Rated Operational Voltage: 230 V, 440 V, 500 V, 690 V Network Frequency: 40...60 Hz [Ie] Rated Operational Current: 12 A <= 440 V, 12 A 500 V, 9 A 690 V [Ics] Rated Service Breaking Capacity: 10 kA 500 V, 4 kA 690 V, 50 kA 230 V, 50 kA 440 V Typical Current Consumption: 130 mA 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD, 140 mA 24 V AC I maximum while closing with LUCA, L...

Manuals

#TitleLanguagesPagesUpdated
1Submittal SheetEN32022-03-27