Belimo Pulse Width Modulation Interface
PTA-250
Categories
Description
Application The PTA-250 converts a single pulse-width modulated input to an analog, 2 to 10 VDC, output to modulate a Belimo -SR actuator. The PTA-250 is available for replacement of existing installations. The …MFT product can replace 100% of the PTA-250 applications, more effectively. Operation A timed contact or solid state closure from the controlling microprocessor controller is converted to a linear analog output with 256 steps of resolution. The last output is held until the PTA-250 receives the end of the next pulsed output. The PTA-250’s output will not wrap around if an excessively long input pulse is received. Four input pulse clock rates are jumper selectable. Normal/Triac input positions are also jumper selectable. The input signal can be optically isolated from the PTA-250 circuit and can accept either positive or negative polarity. A red LED indicator is provided to indicate that power is applied to the PTA-250 and that the microprocessor is functioning. A green LED indicator is provided to ...
Manuals
| # | Title | Languages | Pages | Updated |
|---|---|---|---|---|
| 1 | Product Overview | DE,EN | 12 | 2022-03-23 |