Problem Indicator Cause Corrective Action
Flushvalvedoesnotush.
Nowaterushed. Stop valve is closed Open stop valve
Sensorashes5timesin
quick succession
Flush cycle did not complete Contact Customer Service for further
instruction
No sensor light
Batteries not making contact
Removeandreinstallbatteriescorrectly,
or replace batteries See Battery
installation for reference.
Critically low battery voltage
Sensorashesonceevery5
seconds
Low battery voltage indication
Sensorashesevery30
seconds
Continuous user detection of object
within sensor range
Recalibrate. See Sensor Range
adjustment section for reference.
Sensorashesrapidly
BatteryPowered:
Batteries installed incorrectly.
Remove and reinstall batteries correctly.
See Battery installation for reference.
Hardwired:
Backup batteries installed incorrectly
Remove and reinstall batteries correctly.
See Battery installation for reference.
Hardwired:
Backup Battery not detected.
Installbackupbatteries,orreference
courtesyush&batterydetection
settingssectiontoturnobackup
battery detection.
Sensordetectsuser,three
slowashes&twoquick
ashs,butfailtoushupon
exiting sensor range
User/objectstillinsensoreld
Identifyandremoveanyuserfrom
sensoreld
Reduce sensor range distance (see
Sensor Range Adjustment instructions)
Battery power level too low to activate
ushvalve
Replacebatteries.SeeBatteryInstalla-
tion for reference.
Dirty sensor lens Clean sensor lens with warm water and
mild soap until free of debris
Loose or damaged wire harness Inspectwireharnessandconnection
between electronics and motor
User not detected; no LED
ashes.
Sensor range may need to be adjusted Increasesensorrangedistance(see
Sensor Range Adjustment instructions)
Flush valve is aimed at an angle. Rotateushvalveheadtobe
perpendicular to wall. See Sensor
Angle Adjustment section for adjusting
theushvalvehead.
Manual override button does
notinitiateaush.
Stopvalveisclosed/turnedo. Turn on stop valve.
MOB does not depress Contact Customer Service.
Valve does not evacuate
xture
Insucientvolumeofwaterto
adequatelysiphonxture.
Stop valve is not open enough. Open stop valve for desired volume of
water.
Insucientvolumeorpressureat
supply.
Increaseincomingwatersupply
pressure to minimum 25psi.
Insucientvolumeforinstalledxture Contact Customer Service.
Valveshutsotooquicklyor
shortushes.
Damaged or punctured diaphragm. Installnewdiaphragmreplacement
kit. (See Diaphragm Replacement
and Cleaning Section for replacement
instruction)
Enlargedby-passorice. Installnewdiaphragmreplacement.
(See Diaphragm Replacement and
Cleaning Section for replacement
instruction)
Diaphragm kit is not matched to the
xture.
Installnewdiaphragmreplacement
kit. (See Diaphragm Replacement
and Cleaning Section for replacement
instruction)
Trouble Shooting Guide