User Manual

FV828 Rev. A 02/07/23
Page 7
Unit comes calibrated from the factory. To re-calibrate for a specic environment, follow these steps:
1. While standing next to (not directly in front of) the unit, hold a large and at, nonreective object (e.g. white sheet of paper) in front of
lens at desired calibration distance (12”-60”).
2. Hold a Zurn Magic Magnet at the position shown below and observe the LED light for up 5 seconds and begin to blink once every half
a second.
3. When blinking begins, remove magnet. After a double blink. This signals that the unit has been re-calibrated.
Customized Sensor Range Setting
PROBLEM CAUSE SOLUTION
Status LED blink 1 once every 5
seconds
Low Battery / Incorrect batteries
orientation
Replace and/or install batteries with
the correct orientation.
Not enough water to xture or too
much water to xture.
Diaphragm damaged or valve
control stop improperly adjusted.
Replace diaphragm and/or adjust
valve control stop.
Valve will not operate. Object Lock Sensor range set too
close to EZ Flush, batteries are
dead, or water supply is turned o󰀨.
Adjust Object Lock Sensor, replace
batteries, or turn water on. If the EZ
Flush does not begin to function, call
Customer Service at 1-800-997-3876.
Valve does not shut o󰀨. Dirt or debris preventing diaphragm
from functioning properly.
Remove dirt or debris, check by-pass
hole in diaphragm.
Valve does not ush even after Object
Lock Sensor has been adjusted.
Batteries are dead. Replace batteries. If the EZ Flush
does not begin to function, call Cus-
tomer Service at 1-800-997-3876.
Flush Valve Trouble Shooting Guide
Magic Magnet position
for LEFT hand install
Magic Magnet position
for RIGHT hand install
Status LED
Status LED