Installation Guide
FV806 Rev. A 09/07/21
Page 19
Problem Corrective Action
“Device Not Communicang” posted in plumbSMART Step 1
Verify LoRa Monitor electronics are plugged in / Verify baeries
installed in LoRa Monitor electronics and have sucient charge
(whichever applies). Install new baeries, as needed. Alert on
product’s page in plumbSMART should clear within 1 hour or on
next faucet acvaon. (Refresh web page by clicking on reload
icon in the browser to clear the alert.)
Step 2
If problem sll present, verify gateway is within range of LoRa
Monitor and funconing (see Gateway Troubleshoong secon)
Step 3
If problem is sll present, verify plumbSMART subscripon
status on product page’s Details tab is listed as “Acvated”
NETWORK: Senet
SUBSCRIPTION STATUS: Acvated
LAST HEARD FROM: 07/14/2020, 04:29 PM CDT
If listed as “Deacvated”, contact Zurn Customer Service at
1.855.ONE.ZURN (1.855.663.9876) for assistance.
“Status – Good” posted in plumbSMART and faucet not
actuang
Step 1
Verify LoRa Monitor’s cables are connected to IR sensor
and Faucet actuator electronics. Restore proper electrical
connecon, as needed.
Step 2
Test acvate the faucet.
If problem persists, see Faucet Troubleshoong secon in this
guide for other steps.
“Status – Good” posted in plumbSMART and faucet actuates but
usage event data not appearing in plumbSMART Charts
Step 1
Verify gateway is powered and LoRa Status LED is ON. If not,
apply power per Zurn Gateway Installaon Guide or see
Gateway Troubleshoong secon in this guide for other steps.
Step 2
If problem sll present, verify plumbSMART subscripon status
on product page’s Details tab listed as “Acvated”
NETWORK: Senet
SUBSCRIPTION STATUS: Acvated
LAST HEARD FROM: 07/14/2020, 04:29 PM CDT
If listed as “Deacvated”, contact Zurn Customer Service at
1.855.ONE.ZURN (1.855.663.9876) for assistance.
Step 3
If problem sll present, the LoRa Monitor electronics may be
faulty. Contact Zurn Customer Service at 1.855.ONE.ZURN
(1.855.663.9876) for assistance with addional troubleshoong
steps and, if needed, unit replacement.
Trouble Shooting: LoRa Monitor (-W1/-W2)
For further assistance with troubleshooting, visit https://plumbsmart.zurn.com/app/training