22
Step 1: Shutting Off the Water Supply to the Hydrant
Locate the supply shut-off valve and rotate until water
supply is off.
Step 2: Removing the Faceplate and Adjacent Components
Using 1/8 Allen wrench, remove the five faceplate screws
(22) from head (1) by turning counter clockwise. Remove the
faceplate (18), and nozzle (17).
If the Equa-Balance® seal was not the reason for service -
skip to step 4.
Step 3: Replacing the Equa-Balance® Seal
Remove the current Equa-Balance® seal (21). Check
seal for damage (punctures, rips, etc.). Replace damaged
seal with a new seal (21) observing proper orientation
(EQUA-BALANCE® SEAL SHOULD CUP INWARD IN ITS
REPLACED STATE.)
Step 4: Removing the Internal Operating Assembly
The internal operating assembly (4-8, 10-12, and 23-24) can
be removed by gripping the square end of the operating
screw (5) with a pair of pliers and pulling
straight out.
If the operating screw “O” ring was not the reason for
service - skip to step 6.
Step 5: Replacing the Operating Screw “O” Ring
Remove the operating screw (5) from operating coupling
(7) by turning clockwise and slip the old “O” ring (6) off, and
replace with new “O” ring (6). Reinstall operating screw (5)
into operating coupling (7) by turning counter clockwise.
(NOTE: Lubricate the operating screw (5) threads and the
“O” Ring (6) with Lubriplate FGL-2 if needed).
If the operating screw assembly was not the reason for
service - skip to step 7.
Step 6: Checking Operating Screw Assembly
Remove the operating screw (5) from the operating
coupling (7) by turning clockwise, and using 5/32
Allen wrench, remove set screw (4) by turning counter
clockwise, remove stainless steel ball (24) and check
orientation of “O” ring (23). If not seated properly, reseat,
replace the ball (24) and replace set screw (4) using
Allen wrench and turning clockwise until flush with
operating screw (5) or until tight and flush with operating
screw (5). (NOTE: Lubricate and reinstall as in step 5.)
If the hydrant shutoff washer was not the reason for service
- skip to step 8.
Step 7: Replacing the Hydrant Shutoff Washer
Remove #10 - 24 NC x 5/8 screw (12) using a flat
screwdriver and turning screw (12) counter clockwise,
remove washer (11) and replace with new washer (11)
and new screw (12) turning screw clockwise until tight.
Step 8: Replacing the Internal Operating Assembly
There is a flat or a V-notched boss inside of the hydrant
head (1) that keeps the operating coupling (7) from rotating
when hydrant is turned on and off. With operating screw
(5) turned counter clockwise into operating coupling (7)
until it stops, and making sure that a flat side or corner
of operating coupling (7) lines up with appropriate boss,
reinsert the internal operating assembly into the hydrant.
Step 9: Replacing the Faceplate
Insert nozzle (17) into place and fasten the faceplate (18) to
head (1) using the 1/8 Allen wrench and the five faceplate
screws (22). Rotate the screws clockwise until screws are
snugged tight. (By hand only!)
Step 10: Turning On the Water Supply
Locate the water supply shut-off valve and rotate until water
supply is on.