APPLICATION
Ideal for use where lead free* valves are required. The Zurn Model
P6900-TMV-1 Thermostatic mixing valve is designed to be installed
at the point of use under sinks and sensor faucets to assist in the
prevention of scalding. The valves rapid response and precise
temperature control meet the stringent standards of ASSE 1070
listed for fixtures, sinks, lavatories or bathtubs. The P6900-TMV-1
will mix hot and cold water from the distribution system to a final
safer temperature outlet range of 95-115F (35-46C). The 3/8”
compression fittings make this valve ideal for residential and
commercial applications.
STANDARDS COMPLIANCE
• ASSE® Listed 1070
• CSA® Certified
• NSF® Listed-Standard 61, Section 9, Annex G
LEAD PLUMBING LAW COMPLIANCE
*(0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT)
• Lead Plumbing Law Certified by IAPMO R&T
• Annex G Certified by NSF International
MATERIALS
Body Bronze JIS H5120
CAC902 w/Chrome Plating
ASTM B 456 Service Condition #2
Internal brass ASTM B 927 UNS C27450
Piston Polysufone
Guide Tube Noryl GFN2
Spring 300 Series Stainless Steel
Seals Viton
Checks Acetal Co-Polymer
FEATURES
Sizes: 3/8"
Chrome Plated
Outlet Temp. Range 95-115°F(35-46°C)
Temperature Hot Supply 120-195°F max.
(49-90.5°C)
Temperature Cold Supply 40-75°F(4.4-23.8°C)
Set Temperature Accuracy +/- 3°F(1.78°C)
Max. Working Pressure (inlet) 145 psi
Temperature must be field set
Max. Pressure Differential is 15 psi between Hot & Cold inlets
Flow rate @ 45 psi pressure loss 3.10 gpm
Min. Flow Rate 0.5 gpm
Integral check valves and strainer screen on hot and cold
supply
in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kg.
3/8 9.5 P6900-TMV-1 4 27/32 123 4 3/16 106.3 5 55/64 149 2 1/32 52 2 27/32 72.2 2 1/2 64 1.2 0.6
SIZE MODEL WEIGHT
ACBDFE
DIMENSIONS (approximate)
P6900-TMV-1
DIMENSIONS & WEIGHTS (do not include pkg.)
SINGLE
USE
P6900-TMV-1
PIPING INSTRUCTIONS
The device is designed to be installed at a single outlet.
It may be used to supply individual oultets when there is
sufficient supply pressure. It is suggested to use ball
valves on the hot and cold inlet supplies.
AquaVantage
®
AV
TAG
Rev. B Date: 11/21/11
Dwg. No. 81776 Product No. P6900-TMV-1
Model P6900-TMV-1
Aqua-Gard Thermaostatic Mixing Valve
0
10
20
30
40
50
60
00.511.522.533.544.5
PRESSURE LOSS
(PSIG)
GPM
MODEL P6900-TMV-1