Installation Guide
PROTECTIVE
ENCLOSURE
DIRECTION OF FLOW
12" MIN.
30" MAX.
OPTIONAL LEAD-FREE STRAINER
(MODEL SXL)
Model 950XLT2 LEAD-FREE*
Double Check Valve Assembly (3/4”, 1”, 1 1/4”, 1 1/2” & 2”)
*This product contains a weighted average lead content less than 0.25% for wetted surfaces.
*Meets the requirements of NSF/ANSI 61
INSTALLATION INSTRUCTIONS
CAUTION: Installation of Backow Preventers must be performed by qualied, licensed
personnel. The installer should be sure the proper device has been selected for the
particular installation. Faulty installation could result in an improperly functioning device.
ZURN WILKINS Model 950XLT2 Double Check Valve assemblies are for use on potable
water lines where a health hazard does not exist in the event of a backow situation.
Damage to the device could result wherever water hammer and/or water thermal ex-
pansion could create excessive line pressure. Where this could occur, shock arresters,
check valves and/or pressure relief valves should be installed downstream of the device.
If installation is in a pit or vault, the Backow Preventer must never be submerged in
water because this could cause a cross-connection. Make sure that the pit or vault always
remains dry by providing ample drainage.
1. Before installing a Model 950XLT2 Backow Preventer, ush the line thoroughly to
remove all debris, chips and other foreign matter. If required, a lead-free strainer
should be placed upstream of the Backow Preventer. CAUTION: Do not use a
lead-free strainer in seldom used emergency waterlines such as re lines.
2. Provide adequate space around the installed unit so that the test cocks will be ac-
cessible for testing and servicing.
3. Install valve at least 12 inches above surrounding ood level.
4. Always consult local codes for installation methods, approvals and guidance.
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
Installation Testing Maintenance Instructions
1
INDOOR INSTALLATION
Indoor installation is preferred in areas that
are subject to freezing conditions. All the
basic installation instructions apply to such
installations.
OUTDOOR INSTALLATION
The Model 950XLT2 Backow Preventer
may be installed outdoors only if the device
is protected against freezing conditions.
Exposure to freezing conditions will result
in improper function or damage to the
device. The installation location must be
kept above 32°F. All the basic installation
instructions apply.
PLACING THE MODEL 950XLT2 IN SERVICE
1. Start with both shut-off valves closed.
Slowly open the inlet shut-off valve
until the backow preventer is com-
pletely pressurized.
2. When the unit has been pressurized,
vent any trapped air by slightly open-
ing each of the four test cocks.
3. Slowly open the downstream shut-off
valve. The Model 950XLT2 Double
Check Valve assembly is now in
service.
4. After the Model 950XLT2 has been
properly installed, test the device (see
“TEST PROCEDURES”). If the device
fails the test, remove the rst and
second check valves and thoroughly
ush the device. Clean rubber and
seats of all debris and place unit back
in service.
VERTICAL INSTALLATION
Vertical installation is acceptable in ap-
plications where inlet and outlet piping are
owing vertically upwards. All the basic
installation instructions apply to such instal-
lations. Consult factory for approval status.