FLOW CHARACTERISTICS
TYPICAL INSTALLATION
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturer’s instructions
and the latest edition of the Uniform Plumbing Code. Unless
otherwisespecied,theassemblyshallbemountedata
minimum of 12” (305mm) and a maximum of 30” (762mm)
aboveadequate drains withsufcient side clearancefor
testing and maintenance. The installation shall be made
so that no part of the unit can be submerged.
INDOOR INSTALLATION
(Shown with optional MS)
INDOOR INSTALLATION
(Shown with optional BMS)
SPECIFICATIONS
TheReducedPressurePrincipleBackowPreventershallbeANSI3rd partycertiedtocomplywithstates'leadplumb-
ing law 0.25% maximum weighted average lead content requirement, shall be ASSE® Listed 1013, rated to 180°F and
supplied with full port ball valves. The main body and access covers shall be low lead bronze (ASTM B 584), the seat
ringandallinternalpolymersshallbeNSF®ListedNoryl™andtheseatdiscelastomersshallbesilicone.Therstand
second checks shall be accessible for maintenance without disassembling the relief valve or the entire device from the
line. If installed indoors, the installation shall be supplied with an air gap adapter, integral monitor switch and appropriate
drain.TheReducedPressurePrincipleBackowPreventershallbeaWILKINSModel975XL2TCU.
BATTERY
MONITOR
SWITCH
(OPTIONAL)
AIR GAP
FITTING
12" MIN.
30" MAX.
FLOOR DRAIN
DIRECTION OF FLOW
FLOOR
CENTRAL
STATION
ALARM
PANEL
975XL2
WILKINS
ZURN
ASSE 1013
DRAIN
W/ AIR GAP
DIRECTION OF FLOW
12" MIN.
30" MAX.
CONTACT PANEL WITH
LOW VOLTAGE ELECTRICAL
ALARM, HORN OR LIGHT
975XL2
WILKINS
ZURN
ASSE 1013
Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/8" 1 1 2 3
1/4" 2 2 3 5
3/8" 3 4 6 9
1/2" 5 7 9 14
3/4" 8 12 17 25
1" 13 20 27 40
1 1/4" 23 35 47 70
1 1/2" 32 48 63 95
2" 52 78 105 167
0
20
40
60
80
5
10
15
20
0
50
100
150
200
250
5
10
15
20
Rated Flow (Established by approval agencies)
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
69
PRESSURE LOSS (kpa)
FLOW RATES (l/s)
MODEL 975XL2TCU 3/4", 1", 1 1/4", 1 1/2" & 2" (STANDARD & METRIC)
35
3/4" (20mm)
1" (25mm)
1 1/4" (32mm)
2" (50mm)
103
15.8
12.6
9.56.3
3.25.0
3.82.52
1.26
1 1/2"
(40mm)
137