Installation manual

5
Zone Connections
Zones 1 through 7 can be independently defined as normally closed, normally open or end-of-line resistor zones.
Zone 8 is always a normally closed zone.
For normally closed zones, a zone will go into alarm when a resistance of 2800 or greater is detected. Zone 8
will go into alarm when a resistance of 1000 or greater is detected.
For normally open zones, a zone will go into alarm when a 8400 resistance or less is detected.
For end-of-line resistor zones, a zone will go into alarm when the zone’s resistance drops below 2800 (a short
circuit). A zone will generate a trouble condition when the zone’s resistance rises above 8400 (an open circuit).
Zone Supervision using Zone 8
Zone 8 may be used as a 24-hour Zone to supervise all other zones; refer to the wiring diagram below for wiring
instructions.
The chart below provides the maximum wiring resistance for the various loops described above:
Zone 8 Zones 1 through 7
R1 + R2 = 500 maximum R5 + R6 = 500 maximum
R3 + R4 = 500 maximum R7 = 500 maximum
Bell Supervision using Zone 8
Zone 8 may be used to supervise a Grade A Bell as shown below:
The chart below provides the maximum wiring resistance for the various loops described above:
INSTALLATION
Z1 COM Z2 Z8A Z8B
Zones 1 - 7 Zone 8
R4
R3 R1 R2
A
B
A: EXTERNAL CABINET CONNECTIONS
B: INTERNAL CABINET CONNECTIONS
R5
R6
TO BELL
TERMINALS
BELL
Zone 8 Zones 1 through 7 Bell
R3 = R4 = 500 maximum R1 = R2 = 500 maximum R5 + R6 = 2
Power-Up Procedure
Connect the transformer and wait approximately 5 seconds. Enter a few Keypad commands and activate a zone to
be sure that the panel and Keypad are responding to inputs. If the Keypad does not respond and no LED
indicators come on, check for AC voltage at the AC terminals. If there is 16 VAC present, check that the Keypad
N/C
N/O
N/C
C
C
N/O
N/C
C
Z1 COM Z2 Z8A Z8B
Zones 1 - 7 Zone 8
DETECTOR WITH
TAMPER SWITCH
MAGNETIC
CONTACT
R1
R2
R3
R4
R5
R6
R7
TAMPER
ALARM