Install Instructions
WIRING DIAGRAM 2 – Single Stage Equipment
WIRING DIAGRAM 3 – 24 Volt AC, 40 VA Transformer
Leaving Air Temperature Sensor
The Leaving Air Sensor, Model ZPS, is a remote sensor that is located
in the supply air duct to sense the leaving air temperature of the HVAC
Unit. The ZPS is a high limit protection for the heating and a low limit
protection for the cooling. When zoning, the airflow through the
HVAC Unit is critical. The ZPS protects the equipment in low air flow
situations as well as when by-pass air is being directed back into the
return air duct.
The heating limit is fixed at 180F. The cooling limit is fixed at 40F.
When the ZPS senses heating above its set point, or cooling below its
set point, the MMZ3 will drop both stages of heating or cooling. The
ZPS must sense a 10F fall for heating or rise for cooling before re-
activating the first stages of heating or cooling. If two stage heating or
cooling is being used the second stage timer will start again once the
first stage is re-activated.
The ZPS requires 2 wires from the sensor to the LAT terminals on the
MMZ3 panel. The ZPS probe can also be adjusted for length by
loosening the end nut and sliding the probe thru the mounting plate in
order for the probe to pass through any duct insulation
NOTE: If the ZPS is not used, the NO SENSOR jumper located just
above the LAT terminals must be on the pins.
TROUBLESHOOTING
The MMZ3 is a very simple control to troubleshoot, especially with the
LED indicators. The only other device needed is a simple Volt/Ohm
meter.
The first check is for 24VAC Power to the panel. When there is power
the Green Power LED will be lit. If not check the transformer and the
power supply to it.
Almost all problems can be traded to an external component or wiring
to the MMZ3. While the MMZ3 has been designed to operate under
extreme voltage conditions and is fuse protected, like any computer
the micro-processor can hang up and not operate properly. For these
instances a BOOT button has been installed that re-boots the micro-
processor just like your computer. Pressing this button for a few
seconds and then release it will allow the micro-processor to re-boot
and in most all cases eliminate the problem. If not the following
procedure can help isolate the problem.
Zone(s) Not Calling
Each zone has a Green LED next to the zone relay when it is calling.
The LED being lit shows that the call is being recognized by the
MMZ3. If a zone is supposed to be calling and the Zone LED is not
on, check for 24VAC across the thermostat terminal C and the Y, if a
Cool call, W if a Heat Call, or G if a Fan call. If there is no voltage here
at the panel the panel is not getting the signal from the thermostat.
The problem is mis-wiring, a broken wire or a problem in the
thermostat. To check the zone on the panel, place jumper from R to Y
to simulate a Cool call, R to W to simulate a Heat call, or R to G to
simulate a Fan call. By jumping these terminals the zone call LED will
activate.
Zone(s) Will Not Shut Off
If a zone will not stop calling, the Zone LED should still be on.
Depending on the call disconnect the Y, W or G wire from the terminal
strip. The zone will drop out. Check the thermostat wiring for a mis-
wiring or short that keeps the zone calling.
Damper Motor Checkout
To checkout the dampers, the panel provides 24VAC to the COM and
OPEN terminal when the damper is to be open and 24VAC to COM
and CLOSE when the damper is to be CLOSED. When any zone is
calling and its Green LED is ON, there is 24VAC across COM and
OPEN. The only time a damper will close is when another zone is
calling and its zone is not calling. In this instance there will be 24VAC
across COM and CLOSE terminals.
Refer to the instructions with each damper for their individual
checkout.
Y COMPRESSOR RELAY
G FAN RELAY
W HEAT RELAY
R 24V. TRANSFORMER C
FURNACE CONTROLS
OUTDOOR CONDENSING UNIT
Y
G
W
R
EQUIPMENT
24V TRANS
C
R
C
R
T24 -24V 40VA
TRANSFORMER
Leaving Air Sensor
(Mounted in Supply Air before Zone Dampers)
Model ZPS
LAS Terminals
On Zone Panel
BOOT
Form 2233-0912
MMZ3 Installation and Operating Instructions
©
Copyright Trolex Corporation & ZoneFirst