Submittal Sheet

Zone(s) Not Calling
Each zone has a Green LED next to the zone relay when it is calling.
The LED being lit shows that the call is being recognized by the MMP3.
If a zone is supposed to be calling and the Zone LED is not on, check
for 24VAC across the thermostat terminal C and the Y, if a Cool call, W
if a Heat Call, or G if a Fan call. If there is no voltage here at the panel
the panel is not getting the signal from the thermostat. The problem is
mis-wiring, a broken wire or a problem in the thermostat. To check the
zone on the panel, place jumper from R to Y to simulate a Cool call, R
to W to simulate a Heat call, or R to G to simulate a Fan call. By
jumpering these terminals the zone call LED will activate.
Zone(s) Will Not Shut Off
If a zone will not stop calling, the Zone LED should still be on.
Depending on the call disconnect the Y, W or G wire from the zone
terminal strip on the panel. The call from that zone will drop out when
the thermostat wire is removed. Check the thermostat wiring for a mis-
wiring or short that keeps the zone calling.
If the thermostat wire is disconnected from the proper terminal on the
zone and the zone LED remains lit, re-boot the panel to see if the call
drops. If the call still stays on, turn power off to the panel for 10
seconds and then turn back on. Once powered is restored and the
thermostat is disconected the call should drop from the zone. If not
replace panel.
Damper Motor Checkout Procedure
In order to determine the operation of the damper motors, the panel
motor plug can be checked to determine if power is being supplied
from the panel. If there is power at the motor plug, the problem may
be a broken wire or poor connection in the cord or the motor itself.
To check the power to the motor from the damper plug on the panel,
switch your meter to DC Volts. Note the wires on the plug and check
across either Positive and Neagtive wires. Note that each plug has two
positive leads and two negative leads. Both positive and both negative
leads are wired together. The meter will read either Plus(+) or Minus (-)
12VDC depending if the damper is to be Open or Closed respectively.
DAMPER CLOSED
-12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
VDC
-12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
-12VDC-12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
VDC
DAMPER OPEN
+12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
VDC
+12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
+12VDC+12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
VDC
When using multiple dampers on a single zone, please note to have no
more than 6 dampers on a single zone. Adding dampers beyond the
recommended number may cause all dampers to be slow to operate
and may not fully cycle between open and closed.
Form 2263-0710 MMP3 Installation and Operating Instructions
©
Copyright Trolex Corporation & ZoneFirst