016532
Model
MODEL COMPARISON
Volts Ph Amps Lbs Kg
E840 230 1 1 7. 2 137 62
I840 200 1 20.0 137 62
F840 230 3 10.8 132 60
J840 200 3 12.3 132 60
G840 460 3 5.5 132 60
BA840 575 3 4.5 132 60
I841 200 1 20.0 135 61
E841 230 1 1 7. 2 135 61
J841 200 3 12.3 135 61
F841 230 3 10.8 135 61
G841 460 3 5.5 135 61
BA841 575 3 4.5 135 61
I842 200 1 20.0 135 61
E842 230 1 1 7. 2 135 61
J842 200 3 12.3 135 61
F842 230 3 10.8 135 61
G842 460 3 5.5 135 61
BA842 575 3 4.5 135 61
HEAD CAPACITY CURVE
MODEL 840/841/842
0 40 80 120 160 200 240
70605040302010
0
10
4
8
12
16
20
130
70
60
50
40
30
20
FLOW PER MINUTE
GALLONS
LITERS
TOTAL DYNAMIC HEAD
80
90
28
24
METERS
FEET
100
110
120
32
36
840 841842
TOTAL DYNAMIC HEAD/FLOW
PER MINUTE
SEWAGE
MODEL
Feet
Shut-off Head:
840
Meters Gal. Liters
5
10
20
30 9.1
6.1
3.0
1.5
44
45
167
170
104 ft (31.7 m)
60
50
40
90
80
70
110
100
120
12.2
15.2
18.3
21.3
24.4
27.4
30.5
33.5
36.6
42
36
30 114
136
159
23
16
10 38
61
87
3
--
-- --
--
11
125 ft (38.1 m)
841
Gal. Liters
45 170
45 170
125 ft (38.1 m)
9525
13
4
20 76
49
15
34
32
29
34
34
34
34
129
121
110
129
129
129
129
842
Gal.
34
34
129
129
Liters
59
57 216
223
48
39.5
31 117
150
182
22
13
4.5 17
49
83
59 223
59 223
59 223
59 223
59 223
NOTE: All models are double seal, nonautomatic, 2 HP, and 60 Hz.
• Reversing cutter action can be manual or automatic.
• Circuit in control panel required for automatic reversing action, thermal sensors and moisture probes.
All installation of controls, protection devices and wiring should be done by a qualified licensed electrician. All electrical and safety codes should be
followed including the most recent National Electrical Code (NEC) and the Occupational Safety and Health Act (OSHA).
CAUTION
Electrical Data and Control Panel Selections
Models
Part
Number
Volts Phase HP Amps *Start Pak
**NEMA 4X Control Panels
Simplex Duplex
I841 841-0005 200 1 2 20.0 10-0380 10-1650 10-1652
E841 841-0004 230 1 2 1 7. 2 10-0380 10-1650 10-1652
J841 841-0006 200 3 2 12.3 Not Required 10-1097 10-1125
F841 841-0007 230 3 2 10.8 Not Required 10-1097 10-1125
G841 841-0008 460 3 2 5.5 Not Required 10-1094 10-1122
BA841 841-0009 575 3 2 4.5 Not Required 10-1146 10-1168
I842 841-0005 200 1 2 20.0 10-0380 10-1650 10-1652
E842 842-0004 230 1 2 1 7. 2 10-0380 10-1650 10-1652
J842 842-0006 200 3 2 12.3 Not Required 10-1097 10-1125
F842 842-0007 230 3 2 10.8 Not Required 10-1097 10-1125
G842 842-0008 460 3 2 5.5 Not Required 10-1094 10-1122
BA842 842-0009 575 3 2 4.5 Not Required 10-1146 10-1168
* Capacitors and Start Relay are shipped loose for Field Installation.
** Control Panels include Seal Leak Indication, Visual and Audible High Water Alarm and Dry Contacts. Single Phase Control Panels include Capacitors and Start Relay.
TOTAL DYNAMIC HEAD