INSTALLATION INSTRUCTIONS
RECOMMENDED MODELS
P/N 006355
Notice to installing contractor: Instructions must remain with installation.
FM0447
Rev. A
1114
Supersedes
0414
PREINSTALLATION CHECKLIST - ALL INSTALLATIONS
DATE INSTALLED:
MODEL NUMBER:
EFFLUENT*/SUMP/DEWATERING SEWAGE
55 / 59, 70, 73, 75, 139 Series 211, 212 Series
140 / 4140, 145 / 4145, 160 / 4160 Series 270 / 4270 Series
180 / 4180, 191, 371, 372, 373 Series 280 / 4280, 290 / 4290 Series
Product information presented
here reects conditions at time
of publication. Consult factory
regarding discrepancies or
inconsistencies.
MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
visit our web site:
www.zoeller.com
®
Your Peace of Mind is Our Top Priority
®
* Efuent systems should specify that pumps should not handle solids exceeding
3
/4” in order to prevent large solids from entering leeching elds, mound systems, etc. (70 Series
have
3
/8” solids capability. 50, 140/4140, 371 and 372 Series have ½”, 130 Series has
5
/8”, 145/4145, 160/4160, 180/4180 and 373 models have
3
/4”.) Where code permits, sewage
pumps can be used for efuent systems. Non-automatic pumps with external-level controls are recommended for septic tank efuent applications.
1. Inspect all materials. Occasionally, products are damaged during shipment. If the unit is damaged, contact your dealer before using. DO NOT remove the test plugs from the pump.
2. Carefullyreadtheliteratureprovidedtofamiliarizeyourselfwithspecicdetailsregardinginstallationanduse.Thesematerialsshouldberetainedfor future reference.
SEE BELOW FOR
LIST OF WARNINGS
CAUTION
SEE BELOW FOR
LIST OF CAUTIONS
REFER TO WARRANTY ON PAGE 2.
1. Toreducetheriskofelectricalshock,aproperlygroundedreceptacleorcontrolbox
must be installed in accordance with the governing codes. Never remove ground
pin from plug.
2.Makecertainthatthegroundfaultinterrupterprotectedreceptacleorcontrolboxis
withinthereachofthepump’spowersupplycord.DONOTUSEANEXTENSION
CORD.Extensioncordsthataretoolongortoolightdonotdeliversufcientvoltage
to the pump motor, and they could present a safety hazard if the insulation were to
become damaged or the connection end were to fall into a damp or wet area.
3.Makesurethepump'selectricalsupplycircuitisequippedwithfusesorcircuitbreakers
of proper capacity. A separate branch circuit is recommended, sized according to the
local electrical codes for the current shown on the pump name plate.
4. Testing for ground.Asasafetymeasure,eachelectricaloutletshouldbecheckedfor
ground using a circuit analyzer which will indicate if the power, neutral and ground wires
arecorrectlyconnectedtoyouroutlet.Iftheyarenot,callaqualiedlicensedelectrician.
5. FORYOURPROTECTION,ALWAYS DISCONNECTPUMPFROMITSPOWER
SOURCEBEFOREHANDLING.Ifpumpiswireddirect,de-energizethecircuitat
thecontrolbox.Wearinsulatedprotectiveshoesanddonotstandinwater.Pumps
equippedwitha3-pronggroundplugaredesignedtohelpprotectagainstelectrical
shock.DONOT,UNDERANYCIRCUMSTANCES,REMOVETHEGROUNDPIN.
6. Installation and servicing of the pump, electrical circuits and hardware should only be
performedbyaqualiedlicensedelectrician.
7. Risk of electrical shock. Do not remove power supply cord and strain relief or con-
nect conduit directly to the pump. If the supply cable is damaged, it must be replaced
by the Manufacturer or an authorized Zoeller Service Station to avoid a hazard.
8. Pumpcontainsoilwhichbecomespressurizedandhotwhenoperating.Allow2½
hours after disconnecting before attempting service.
9. Pumpisnotintendedforpotablewaterduetopossiblecontaminationbyoilcontained
in the pump.
10. Risk of electric shock.Thesepumpshavenotbeeninvestigatedforuseinswimming
pools and marine areas.
11.AccordingtothestateofCalifornia(Prop.65),thisproductcontainschemicals
knowntothestateofCaliforniatocausecancerandbirthdefectsorother
reproductive harm.
1. Checktobesureyourpowersourceiscapableofhandlingthevoltagerequirements
of the motor, as indicated on the pump name plate.
2. Theinstallationofvariableleveloatswitchesistheresponsibilityoftheinstalling
party,andcareshouldbetakenthatthetetheredoatswitchwillnothanguponthe
pump apparatus or pit peculiarities and is secured so that the pump will shut off. It is
recommendedtouserigidpipeandttingsandthepitbe18"orlargerindiameter.
3. Vent hole.Itisnecessarythatallsubmersiblesump,efuent,andsewagepumps
capableofhandlingvarioussizesofsolidwastebeofthebottomintakedesignto
reducecloggingandsealfailures.Ifacheckvalveisincorporatedintheinstallation,
a
3
/16"ventholemustbedrilledinthedischargepipebelowthecheckvalveandpit
covertopurgetheunitoftrappedair.Ventholeshouldbecheckedperiodicallyfor
clogging.TheventholeonaHighHeadapplicationmaycausetoomuchturbulence.
If you choose not to drill a vent hole, be sure the pump case and impeller is covered
withliquidbeforeconnectingthepipetothecheckvalve.NOTE:THEHOLEMUST
BEBELOWTHEBASINCOVERANDCLEANEDPERIODICALLY.Waterstreamwill
be visible when pump is operating.
4. Pumpshouldbecheckedfrequentlyfordebrisand/orbuildupwhichmayinterfere
withtheoat“on”or“off”position.Repairandserviceshouldbeperformedbyan
Authorized Zoeller Service Station only.
5. Maximumoperatingtemperatureforstandardmodelpumpsmustnotexceed130°F
(54°C).Maximumoperatingtemperaturesfor70seriesandmodel211mustnot
exceed110°F(43°C).Maximumoperatingtemperaturesfor73,75,212series
andmodel211mustnotexceed104°F(40°C).
6. DonotoperateapumpinanapplicationwheretheTotalDynamicHeadislessthan
theminimumTotalDynamicHeadlistedonthePumpPerformanceCurves.
7. Forhealthreasons,donotunplug,turnoff,ordisablepumpandusepumptank
systemasawaytollupasinkorlaundrytray,etc.
8. PumpsmustbeinstalledinaccordancewiththeNationalElectricalCodeandall
applicablelocalcodesandordinances.Pumpsarenottobeinstalledinlocations
classiedashazardousinaccordancewithNationalElectricCode,ANSI,NFPA70.
NOTE:Pumpswiththe"UL"markandpumpswiththe"US"markaretestedtoULstandard
UL778.CSAcertiedpumpsarecertiedtoCSAstandardC22.2No.108.
Register your
Zoeller Pump Company
Product on our website:
http://reg.zoellerpumps.com/
NOTICE: VENT HOLE FOR
CHECK VALVE
SEE #3 IN CAUTION SECTION
BELOW AND #4 ON PAGE 3