Product Overview
© Copyright 2007 Zoeller Co. All rights reserved.
THREE PHASE SIMPLEX CONTROL PANEL FEATURES
• 208-230-460-575 Volts.
• Nema 4X - watertight enclosure with lockable latch.
• Hand-off-toggle switch.
• Green pump run light.
• Alarm test & silence switches.
• Red alarm beacon and audible alarm for a high water condition
(83 to 85 decibel rating).
• Motor protection switch with overload protection.
• Magnetic starter.
• Numbered terminal strip for connecting pumps and variable level fl oat
switches.
• Dry auxiliary contacts for remote alarm devices.
• Three fl oat operation (fl oats not included - See FM0526).
• UL Listed.
• The use of off-the-shelf components provide for relatively easy fi eld main-
te nance and repair.
• 2 Year Warranty.
Three Phase -
Dead Front Cover
R
L
U
PUMP POWER SUPPLY
CONTROL & ALARM
POWER SUPPLY
NOTE: ALARM - CONTROL
CIRCUIT SHOULD BE
SEPARATE FROM
PUMP POWER
2" OR 3" DISCHARGE PIPE
FLOOR FLANGE
ZOELLER FIBERGLASS
OR POLYETHYLENE BASIN
ZOELLER FLOAT SWITCH
ZOELLER SEWAGE PUMP
SIMPLEX CONTROL PANEL
ZOELLER UNICHCEK
CHECK VALVE (2" OR 3")
4" HUB INLET
"ALARM" LEVEL SET
ABOVE "ON" FLOAT AND
BELOW INLET.
"ON" LEVEL PUMP OPERATION
IS EACH CYCLE MAXIMIZED
BASED ON DEPTH AND VOLUME
MINIMUM "OFF" LEVEL
DISCONNECT
OF BASIN
(SINGLE PHASE ONLY)
(SINGLE PHASE ONLY)
5"
ALARM LIGHT
SK1734
SEQUENCE OF OPERATION FOR SIMPLEX PANEL
1. Operation can begin after the following:
- Correct voltage is supplied to Panel
- A good ground is supplied to Panel
- Pump is connected correctly to Panel
- Panel Circuit Breaker is closed
- Floats are installed properly
- Overload Protection is adjusted to Pump nameplate amps
- Pump HOA Switch is set to “Auto”
2. When the “Stop” and “Start” fl oats are closed the Pump will energize and the
External Pump Run Light will illuminate. The Pump will remain op er a tion al
until the “Stop” fl oat opens.
3. In the event the liquid level continues to rise the “Alarm” fl oat will be closed.
When the “Alarm” fl oat is closed the following will occur:
- The External High Water Light will illuminate
- The Audible High Water Horn will sound
- The Auxiliary Dry Contacts will close
4. The Audible High Water Horn can be silenced by pressing the Alarm
Silence Button. When the “Alarm” fl oat is opened the External High
Water Light, Audible High Water Horn and Dry Auxiliary Contacts
will be reset.
*A Three Phase Panel has a multi-tap transformer with sec ond ary
fusing.
All electrical sys tems must be in stalled by a qualifi ed
li censed elec tri cian according to the Na tion al Elec tri cal Code. (See
sec tion 430-71 through 430-113 plus any oth ers that apply)
Refer to FM1228 and FM1705 for correct selection of Simplex
Panels.
THREE PHASE SIMPLEX PUMP CONTROL PANELS
MODEL # DIMENSIONS VOLTS AMP RANGE
10-1074 12 X 10 X 6 208/230/460 1.0 - 1.6
10-1076 12 X 10 X 6 208/230/460 1.6 - 2.5
10-1078 12 X 10 X 6 208/230/460 2.5 - 4.0
10-1080 12 X 10 X 6 208/230/460 4.0 - 6.3
10-1082 12 X 10 X 6 208/230/460 6.0 - 10.0
10-1083 12 X 10 X 6 208/230/460 9.0 - 14.0
10-1084 12 X 10 X 6 208/230/460 13.0 - 18.0
10-1086 12 X 10 X 6 208/230/460 17.0 - 23.0
10-1132 12 X 10 X 6 575 1.6 - 2.5
10-1134 12 X 10 X 6 575 2.5 - 4.0
10-1136 12 X 10 X 6 575 4.0 - 6.3