Install Instructions

FIGURE 1
CORDS SECURED
"ON"
"OFF"
LEVEL
LEVEL
TO DISCHARGE
PIPE
RANGE
PUMPING
FLOAT
CLAMPS
THE "ON" LEVEL IS
APPROXIMATELY 4"
ABOVE MOUNTING
LOCATION
THE "OFF" LEVEL IS
APPROXIMATELY 4"
BELOW MOUNTING
LOCATION
MECHANICAL FLOAT SWITCH
10-1964, 10-1965, 10-1966, 10-1967
CORDS SECURED
"ON"
"OFF"
LEVEL
LEVEL
TO DISCHARGE
PIPE
FLOAT
CLAMPS
MERCURY FLOAT SWITCH
10-0229, 10-0230, 10-1209, 10-1210
NARROW ANGLE
FLOAT SWITCHES
RANGE
PUMPING
SK308B
READ ALL INSTRUCTIONS BEFORE INSTALLING - ALL APPLICATIONS
Make sure the pump electrical supply circuit is equipped with fuses or circuit breakers of proper capacity. A separate branch circuit is recommended, sized
according to the National Electrical Code for the current shown on the pump name plate.
FOR YOUR PROTECTION ALWAYS DISCONNECT PUMP FROM ITS POWER SOURCE BEFORE HANDLING. Single phase pumps are supplied with
a 3-prong grounded plug to help protect you against the possibility of electrical shock.
DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE GROUND PIN. The 3-prong plug must be inserted into a mating 3-prong grounded receptacle.
If the installation does not have such a receptacle, it must be changed to the proper type, wired and grounded in accordance with the National Electrical Code and all ap-
plicable local codes and ordinances.
FIGURE 2 FIGURE 3
FIGURE 4
NOTICE TO INSTALLER: Instructions must remain with installation.
P/N008620
S.J.E. 1011888C
SECTION: 6.10.110
FM0478
0211
Supersedes
0406
A) Remove (cut) Piggyback
Plug from Variable Level
Float Switch. Remove ap-
prox. 3½” of Cord Jacket
and 1” insulation from
Wires.
B) Wire Switch into Circuit as
shows.
C) Return to Instructions.
D) Installation must be in
agreement with the
National Electric Code
and all local codes.
Zoeller 10-0229, 10-0230, 10-1209, 10-1210, 10-1964, 10-1965, 10-1966 and 10-1967 Double Piggyback Variable Level Float Switches are designed for use
with the appropriate voltage and horsepower, nonautomatic, single phase, Zoeller pumps.
Use 10-0229, 10-1209, 10-1964 and 10-1966 for 115V and 10-0230, 10-1210, 10-1965 and 10-1967 for 230V. All can be used as a control switch for a magnetic
or combination starter. Maximum temperature must not exceed 140°F. NOTE: UL Recognized and CSA approved. NOTE: Consult factory for controlling units over 1½ HP with vari-
able level oat switch.
INSTALLATION INSTRUCTIONS
1. Decide the desired pumping range for your installation. (See Fig.
1.) Secure the oat cable clamps to the discharge pipe at the
distance you desire. (See clamp detail in Fig. 6 on next page).
The oat labeled “TOP” must be on top. (The cable clamps are
releasable, which permits readjustment and removal.)
NOTICE: Do not adjust “Off’’ Level below discharge on pump.
2. Insert the piggyback plug from the switches into a standard grounded
outlet of proper voltage. For automatic operation plug the pump
directly into the piggyback plug. (Pump can be manually operated
by bypassing piggyback plug.) See Fig. 2.
NOTICE: For installation utilizing a watertight junction box or
similar connections, see Figure 3.
NOTICE: For installation as a control switch for magnetic or
combination starter, see Figure 4.
3. Securely tape or clamp both piggyback switch cord and pump
cord to the discharge pipe, clear of oat operation. (See Fig. 1.)
Excess cord should be coiled and fastened to the discharge pipe.
4. Clean basin free of debris after installation.
5. Check and test your installation. Fill basin with water and allow pump to cycle to insure proper range and operation. NOTICE: For installation utilizing a Piggyback Float Switch
connection use Zoeller Qwik-Box. See FM1420
ZOELLER DOUBLE PIGGYBACK VARIABLE LEVEL FLOAT SWITCH
10-0229, 10-1209 10-1964, 10-1966 - 115V/1HP - 15 FT. cord 10-0230, 10-1210, 10-1965 and 10-1967 - 230V/2 HP - 15 FT. cord
Designed for EFFLUENT, SEWAGE AND DEWATERING applications.
SK308C
© Copyright 2011 Zoeller Co. All rights reserved.
PUMP PLUG
SWITCH PLUG
AUTOMATIC
OPERATION
MANUAL
OPERATION
SK308A
SK378B
Product information presented
here re ects con di tions at time
of publication. Consult factory