Specifications
2.3.4 Outdoor Installation
The Legacy Model LRZ electronic heater can be
installed in the low-prole conguration as received
from the factory, or with an optional factory approved
vent cap for high wind applications..
Locate the heater in an open, unroofed area. Do
not install the heater under a deck. Do not locate the
heater below or adjacent to any doors, glass openings,
louvers, grills, etc., which connect in any way with an
inhabited area of a building, even though the access
might be through another structure (e.g., a garage or
utility room).
In the United States the vent system shall
terminate at least four (4) ft (1.2 m) below, four (4) ft
(1.2 m) horizontally from, or one (1) ft (300 mm) above
any door, operable window, or gravity inlet into any
building. In Canada, the heater must be installed so that
the exhaust point of the heater is at least 10.0 feet (3.0
m) from any building opening. See Figure 3.
United States
Do not install the heater with the top of the vent
assembly within 4 feet (1.22 m) horizontally, 4
feet (1.22 m) below or less than 1 ft (300 mm)
above of any opening into a building.
WARNING
Canada
Do not install the heater with the top of the vent
assembly within 10 feet (3.05 m) of any opening
into a building.
Lorsque vous installez l’appareil de chauffage,
assurez-vous que l’ouverture d’aération se trouve
à un minimum de 10 pieds (3.05 m) de toute
ouverture d’un bâtiment.
AVERTISSEMENT
The top surface of the heater must be at least
three (3) feet above any forced air inlet, or intake ducts
located within 10 feet horizontally.
If the heater is installed under an overhang, there
must be a minimum clearance of ve (5) feet (1.5 m)
above the top of the heater and the structure should not
overhang the heater more than 12 inches (0.30 m). The
area under the overhang must be open on three sides.
This prevents combustion gases from being diverted
into living areas through doors, windows, or gravity
inlets.
Ne pas installer ce chauffe-piscine sous une saillie mesurant
moins de 3 pi de hauteur. La partie sous la saillie doit être
ouverte sur 3 côtés.
If the heater is installed close to a structure, protect
it from rain water runoff with rain gutters on the roof or
other measures. Do not locate the heater near irrigation
sprinkler systems that could spray water on it. Water
from sprinklers may cause damage to controls and
electronic components.
Avoid locations where wind deection off nearby
structures might cause downdraft conditions. Where
downdraft conditions exist, locate the heater at least
three (3) feet (0.91 m) from vertical surfaces (e.g.,
nearby buildings and walls).
In Florida, it is required that the heater be securely
fastened to the equipment pad. Use size
1/4" x 2-1/4" long galvanized or plated concrete screws
and washers at each of the four tabs located at the base
of the heater. Mounting the appliance in this manner
meets the applicable requirements of the Florida
Building Code.
Mounting screws are not provided with this heater.
After placing the heater on the equipment pad, drill a
hole in the concrete at each of the four tabs on the feet of
the heater. (The correct size drill bit is usually provided
with the concrete screws when purchased). Place a
screw in each of the holes and fasten the heater to the
equipment pad. See Figure 4. Do not over-torque the
screws.
2.3.5 Indoor and Outdoor Shelter
Installations
An outdoor shelter (Canada only) is an unoccupied
enclosure which does not communicate directly with
occupied areas. All indoor installations and outdoor
shelter installations require a factory approved draft
hood. The draft hood must be installed without
modication and in accordance with the instructions
provided by the manufacturer.
Une remise extérieure (au Canada seulement) est un endroit
inoccupé qui ne communique pas directement avec les
endroits occupés. Toutes les installations intérieures et remises
extérieures exigent l’addition d’une cheminée approuvée
par le manufacturier. La cheminée doit être installée sans
aucune modication et selon les exigences fournies par le
manufacturier.
1/4” X 2-1/4”
GALVANIZED OR PLATED
CONCRETE SCREWS
Figure 4. Anchor Heater To Equipment Pad
Page 10