Technical data
LED Indicators
14-Slot Shelf
Chapter 2
90
Alarm Display Panel Telco Alarms
The following section describes some of the alarm interfaces, LEDs, and other functions.
Telco Alarm Interface
The ADP provides a Telco Alarm interface on the DB15-male connector. The Telco Alarm interface relay
circuits are capable of carrying 60 VDC or 1 A with a max. rating of 30 VA. The ADP accepts timed pulse
inputs for clearing Minor and Major alarm states.
NOTE There is no test for the Critical state.
Reset is accomplished by asserting a voltage differential from 3.3 V to 48 V for between 200 and 300 ms. The
acceptance voltage range is from 0 to 48 VDC continuous (handles up to 60 VDC at a 50% duty cycle). The
current drawn by a reset input does not exceed 12 mA.
Telco Alarm LEDs
The Shelf Alarm Display provides the Telco Alarm LEDs. These LEDs indicate presence of Critical, Major
and Minor alarms as follows:
Telco Alarm Cutoff Pushbuttons
The Telco Alarm Cutoff push button (RST) on the Shelf Alarm Display activates the Alarm Cutoff (ACO)
state. When ACO is activated, the active Alarm LEDs blink and all of the alarm relays are deactivated.
22 RST_PB Signal from Alarm Cutoff Push Button
23 LED_FT-FAIL_1 Signal to Fan Tray Left Alarm LED
24 LED_FT_FAIL_2 Signal to Fan Tray Center Alarm LED
25 LED_FT_FAIL_3 Signal to Fan Tray Right Alarm LED
26 LED_FT_OK_1 Signal to Fan Tray Left OK LED
27 LED_FT_OK_2 Signal to Fan Tray Center OK LED
28 LED_FT_OK_3 Signal to Fan Tray Left OK LED
Table 2-6 Telco Alarm LEDs
State Description
Off No alarm triggered
On Alarm triggered
Blinking Alarm Cutoff (ACO) is activated
Table 2-5 Alarm Display Panel Horizontal Board Pin Assignment (Continued)
Pin Signal Name Description