Technical data

Field Replaceable Unit Removal and Replacement
14-Slot Shelf Chassis and Backplane
Chapter 1
60
Figure 1-18 14-Slot Shelf, Rear View (Blade Cage Empty)
Step 1. Shut down normal operation of the HP bh5700ATCA 14-Slot Blade Server.
Step 2. Disconnect/disable all external input power sources to both PEMs.
WARNING Electrical Shock Hazard. Power is always present at the PEM power terminals
unless the external power source is turned off. Disable/disconnect all power domain
circuit breakers in the OFF (O) position before completing any of the following steps.
Failure to follow electrical safety precautions may result in personal injury.
Step 3. Record all current console and Ethernet cable hookup configurations for all installed blades and the
Shelf, and set aside as a reference for configuring the replacement Shelf.
Step 4. Disconnect all external power supply input cables from the PEMs and protective earth ground
cables from the 14-Slot Shelf chassis.