Technical data

Field Replaceable Unit Removal and Replacement
14-Slot Shelf Chassis and Backplane
Chapter 1
58
14-Slot Shelf Chassis and Backplane
Although the 14-Slot Shelf chassis with backplane is replaced as an individual FRU, the replacement 14-Slot
Shelf chassis and backplane will contain a full complement of chassis components when delivered. These
components include:
Both Shelf Management Modules, or “Shelf Managers” (ShMMs)
Both Power Entry Modules (PEMs)
All Fan Modules
Air Filter Tray and Filter Element
The Alarm Display Panel
The Alarm Connector Panel
Both Chassis Data Modules (Backplane SEEPROM Assemblies)
CAUTION Possible 14-Slot Shelf chassis data loss. The Chassis Data Modules must be removed from the
defective 14-Slot Shelf and installed in the replacement 14-Slot Shelf chassis in order to retain
your 14-Slot Shelf chassis configuration data.
Removing the 14-Slot Shelf Chassis and Backplane
CAUTION Possible 14-Slot Shelf chassis configuration data loss. In order to retain original chassis
configuration data when the 14-Slot Shelf chassis and backplane are replaced as a FRU, the
original 14-Slot Shelf Backplane SEEPROM Assemblies must be removed from the defective
chassis and installed in the replacement 14-Slot Shelf chassis.
CAUTION Electrostatic Discharge Hazard. Observe all ESD safety precautions while completing this
procedure. Failure to follow ESD safety precautions could result in damage to the 14-Slot Shelf
and equipment.
NOTE Removing and replacing the 14-Slot Shelf chassis is a cold-swap procedure. There are no hot
swap requirements for this procedure.
To remove the chassis and backplane from the 14-Slot Shelf system, complete the following steps (refer to
Figure 1-17 and Figure 1-18):