Technical data
Field Replaceable Unit Removal and Replacement
14-Slot Shelf Chassis and Backplane
Chapter 1
58
14-Slot Shelf Chassis and Backplane
Although the 14-Slot Shelf chassis with backplane is replaced as an individual FRU, the replacement 14-Slot
Shelf chassis and backplane will contain a full complement of chassis components when delivered. These
components include:
• Both Shelf Management Modules, or “Shelf Managers” (ShMMs)
• Both Power Entry Modules (PEMs)
• All Fan Modules
• Air Filter Tray and Filter Element
• The Alarm Display Panel
• The Alarm Connector Panel
• Both Chassis Data Modules (Backplane SEEPROM Assemblies)
CAUTION Possible 14-Slot Shelf chassis data loss. The Chassis Data Modules must be removed from the
defective 14-Slot Shelf and installed in the replacement 14-Slot Shelf chassis in order to retain
your 14-Slot Shelf chassis configuration data.
Removing the 14-Slot Shelf Chassis and Backplane
CAUTION Possible 14-Slot Shelf chassis configuration data loss. In order to retain original chassis
configuration data when the 14-Slot Shelf chassis and backplane are replaced as a FRU, the
original 14-Slot Shelf Backplane SEEPROM Assemblies must be removed from the defective
chassis and installed in the replacement 14-Slot Shelf chassis.
CAUTION Electrostatic Discharge Hazard. Observe all ESD safety precautions while completing this
procedure. Failure to follow ESD safety precautions could result in damage to the 14-Slot Shelf
and equipment.
NOTE Removing and replacing the 14-Slot Shelf chassis is a cold-swap procedure. There are no hot
swap requirements for this procedure.
To remove the chassis and backplane from the 14-Slot Shelf system, complete the following steps (refer to
Figure 1-17 and Figure 1-18):