Technical data
Field Replaceable Unit Removal and Replacement
Air Filter
Chapter 1
44
Air Filter
The 14-Slot Shelf air filter is located near the bottom front of the Shelf, immediately beneath the blade slots
(Figure 1-8). The air filter is a hot-swap unit, and can be removed and replaced while the
14-Slot Shelf is in normal operation. There is no voltage present at the air filter element and filter tray.
WARNING Electrical Shock Hazard. System power is applied to the 14-Slot Shelf at all times during this
hot-swap removal and replacement procedure. Observe all electrical safety procedures while
working on this hot-swap unit.
Figure 1-8 Filter Tray Extended, 14-Slot Shelf Front View
Air Filter Element Replacement Schedule
The air filter element must be removed and replaced a minimum of every three months when operating in a
computer room with a raised-floor environment. Your environment may require a more frequent change
schedule.
Removing the Air Filter
IMPORTANT When the air filter tray is removed during system operation, the removal event is recorded in
the System Event Log (SEL) of the 14-Slot Shelf as a default reaction. Note that the ShMM
software can be pre-set to react to this event.