Technical data

LED Indicators
HP bc2100 ATCA Server Blade
Chapter 2
117
3 Voltage or temperature
sensors are outside of
threshold
1. Examine the other Blades in the Shelf. If all of the
Healthy LEDs are illuminated red, there may be a
power failure on one of the two redundant power
busses. Make sure both power busses to the ATCA are
on and Check both Power Entry Modules for proper
operation.
2. If voltage and temperature sensors are within
threshold, this indicates an internal hardware fault and
inoperable IPMC.
3. Verify that other components are not experiencing the
same failure. If they are a chassis level problem may be
the cause, replace the chassis.
4. If the Server Blade is the only FRU experiencing
exceeding thresholds, try pressing the Reset Button
5. If the Reset Button does not correct the problem,
replace Server Blade.
4 The switch is held in
RESET.
1. The Shelf Manager is holding the Server Blade as
RESET. Follow the troubleshooting tips in "Diagnosing
a Failed Shelf Manger Activation" in the Server Blade
manual to extract the Shelf Manager information for
further analysis.
2. If the Server Blade is still being held at RESET after
troubleshooting the Shelf Manager, replace the Server
Blade.
5
Table 2-33 HP bc2100 ATCA Server Blade LED Tips (Continued)
Tip Symptom Action