Installation guide

Connecting Protective Earth Ground and External Power to the Shelf
Connecting Protective Earth Ground and External Power to the Shelf
Chapter 4
38
Connecting the Power and Return Cables
WARNING Ensure that each power domain supply circuit breaker is switched OFF while
completing the following power connection procedure. Failure to comply can result
in personal injury.
To connect external power and voltage return (VRTN) leads to the 14-Slot Shelf, complete the following steps:
Step 1. On the rear of the 14-Slot Shelf, remove the PEM A Terminal Block Cover and connect the four
PEM A independent domain power cables and four return lines as shown in Figure 4-4. The four
cables and terminals on the left are the power domain leads, and the four cables and terminals on
the right are the return lines for the PEM.
Figure 4-4 PEM Power Lead and Return (RTN) Connections
CAUTION Make certain to connect matching power supply domain 1 lead to power domain 1
terminal lug on the PEM, matching lead 2 to terminal lug 2, and so on. Also ensure
that power domain VRTN lines are matched to respective connections on each PEM.
See Figure 4-4 and Figure 4-5.
NOTE In a typical telecommunications environment, the VRTN path of the -48 VDC supply
is grounded to protective earth (PE) of the building.
Step 2. Replace and secure the PEM A terminal block cover when all power leads and VRTN lines have
been attached.
Step 3. Remove the PEM B terminal block cover (see Figure 4-5) and connect the four PEM B independent
domain power leads and VRTN lines from the redundant power supply, using the same procedure
as above, for PEM A.
Return Cable
s
(Black)
Power Lead
Cables