Installation guide
Connecting Protective Earth Ground and External Power to the Shelf
Connecting Protective Earth Ground and External Power to the Shelf
Chapter 4
34
Connecting Protective Earth Ground and External Power to the Shelf
This chapter provides information on connecting protective earth ground and external system power to the
installed 14-Slot Shelf.
WARNING Disconnect all power cords to completely remove power. This is a shock hazard.
IMPORTANT Overcurrent protection for the system must be provided at the installation site at not less than
125% of the load for each supply circuit. Due to safety issues when servicing the system, only
one blade should be removed at a time and any slots not containing a blade must have a cover
plate installed.
NOTE System DC power requirements are located on the side of the ATCA chassis. HP PN:
AD171-2000A on the power label is equivalent to the FCLSB-0602.
Connecting the Shelf to Earth Ground
WARNING Protective ground must be connected to the 14-Slot Shelf before connecting any
external power. This is a high voltage hazard if not connected.
On the right-rear of the 14-Slot Shelf, connect an earth grounding cable to the two grounding lugs located
above the power entry module A (PEM A). See Figure 4-1 and Figure 4-2.
Recommended minimum specifications for the grounding cable and its connection include the following:
• Recommended Minimum Wire Size: AWG6
• Recommended Terminals: Use only double lug terminals, with a 45
o
angle.