Instruction manual
IMNZC21-E1
3
3.2 Terminal Configuration
Power supply
Control output
Input
NO: Normally open
6
7
8
9
10
14
12
1
2
3
4
5
AC
24V
DC
100−240V
AC
24V
7
6
7
6
7
6
L
N
+
−
L
N
CT input
Current
transformer
11
12
CT
TC input
+
−
TC
8
9
RTD input
A
B
B
RTD
8
9
10
C100
13
11
Alarm output
Relay contact
ALM1
ALM2
NO
NO
3
2
1
A
larm 2, Heater break
alarm or Control loop
break alarm
A
larm 1 or
Control loop
break alarm
OUT
T2
T1
G
3
5
4
Trigger for
triac drive
OUT
+
−
5
4
Voltage pulse/
Current
Relay contact
NO
OUT
4
5
•
Terminals which are not used according to
the controller type are all removed.
•
When control output is trigger output for triac
driving, the number of alarm output points
becomes 1.
•
Use the solderless terminal appropriate to
the screw size.
Screw size: M3 x 6
Recommended tightening torque:
0.4 N
m [4 kgf
cm]
Maximum allowance: 0.7 N
m [7 kgf
cm]
6.2 mm (0.24 inch) or less
Voltage/Current
+
−
8
9
Power supply
Control output
NO: Normally open
NC: Normally closed
W, A action types
Relay contact
F, D action types
NC
NO
OUT
6
7
8
C400, C410, C900
1
2
3
4
5
6
7
8
10
11
9
12
13
14
15
16
17
18
19
20
22
23
21
24
Ground
1
8.1 mm (0.32 inch) or less
•
Terminals which are not used according to the
controller type are all removed.
•
An example of the C900 is described here, the
same wiring examples also apply to C400/C410.
(Terminal numbers 17 to 24 are not provided for
C400/C410.)
•
Use the solderless terminal appropriate to the
screw size.
Screw size: M3 x 8
Recommended tightening torque:
0.4 N
m [4 kgf
cm]
Maximum allowance: 1.0 N
m [10 kgf
cm]
OUT
T2
T1
G
6
8
7
Trigger for
triac drive
OUT
+
−
8
7
Voltage pulse/
Current
Relay contact
NO
OUT2
NO
OUT1
5
6
7
8
OUT2
OUT1
+
+
−
−
5
6
7
8
TC input
−
+
TC
15
16
RTD input
B
B
A
RTD
14
15
16
Input
Current
transformer input
13
12
CT
Alarm output
100
−
240V
AC
24V
DC
24V
AC
3
3
2
3
2
L
N
+
−
L
N
Relay contact
ALM1
ALM2
NO
NO
11
10
9
A
larm 1 or
Control loop
break alarm
A
larm 2, Heater break
alarm or Control loop
break alarm
CT input
Voltage pulse/
Current
Voltage/Current
−
+
15
16
2
C700
1
2
3
4
5
6
7
10
8
11
12
13
14
15
16
18
19
17
20
6.2 mm (0.24 inch)
or less
8.1 mm (0.32 inch)
or less
Screw size: M3 x 6
Terminals Nos. 1 to 10
(Power terminals, Alarm
terminals and Out
p
ut terminals
)
Screw size: M3 x 8
Terminals Nos. 11 to 13
(Input terminals)
9
Power supply
Control output
NO: Normally open
NC: Normally closed
W, A action types
Relay contact
F, D action types
NC
NO
OUT
6
7
8
Ground
1
•
Terminals which are not used according to
the controller type are all removed.
•
Use the solderless terminal appropriate to the
screw size.
Recommended tightening torque:
0.4 N
m [4 kgf
cm]
Maximum allowance: 1.0 N
m [10 kgf
cm]
OUT
T2
T1
G
6
8
7
Trigger for
triac drive
OUT
+
−
8
7
Voltage pulse/
Current
Relay contact
NO
OUT2
NO
OUT1
5
6
7
8
OUT2
OUT1
+
+
−
−
5
6
7
8
100
−
240V
AC
24V
DC
24V
AC
3
3
2
リレ 接点
2
3
2
L
N
+
−
L
N
Voltage pulse/
Current
TC input
−
+
TC
12
13
RTD input
B
B
A
RTD
11
12
13
Input
Current
transformer input
20
1
9
CT
Alarm output
Relay contact
ALM1
ALM2
NO
NO
10
9
8
A
larm 1 or
Control loop
break alarm
A
larm 2, Heater break
alarm or Control loop
break alarm
CT input
Voltage/Current
−
+
12
13
Specifications
Input:
Input type:
Thermocouple: K, J, R, S, B, E, T, N, PLII,
W5Re/W26Re, U, L
Input impedance: Approx. 1 MΩ
RTD: Pt100, JPt100
Voltage: 0 to 5 V DC, 1 to 5 V DC
Input impedance: 250 kΩ or more
Current: 0 to 20 mA DC, 4 to 20 mA DC
Input impedance: Approx. 250 Ω
Sampling cycle:
0.5 seconds
Input range:
See
Input range table
Control method:
PID control
ON/OFF, P, PI, or PD actions is available
Control output:
Relay contact output: 250 V AC, 3A (Resistive load)
Electrical life:
300,000 times or more (Rated load)
Voltage pulse output: 0/12 V DC
(Load resistance 600 Ω or more)
Current output: 4 to 20 mA DC
(Load resistance 600 Ω or less)
Trigger output (for triac driving):
Zero cross method for medium capacit
y
triac driving (100 A or less)
Load voltage used:
100 V AC line, 200 V AC line
Load used: Resistive load
Memory backup:
Backed up by Nonvolatile Memory
Number of write times:
Approx. 100,000 times
Data storage period:
Approx. 10 years
Power:
Power supply voltage:
85 to 264 V AC (Power supply voltage
range), 50/60 Hz
Rating: 100 to 240 V AC
21.6 to 26.4 V AC (Power supply
voltage range), 50/60 Hz
Rating: 24 V AC
21.6 to 26.4 V DC (Power supply
voltage range)
Rating: 24 V DC
Power consumption:
6 VA max. (at 100 V AC)
9 VA max. (at 240 V AC)
6 VA max. (at 24 V AC)
145 mA max. (at 24 V DC)
Weight:
C100: Approx. 170 g
C700: Approx. 250 g
C400/C410: Approx. 260 g
C900: Approx. 340 g
Alarm output:
Relay contact output:
250 V AC, 1A (Resistive load)
Electrical life: 50,000 times or more
(Rated load)
Heater break alarm function:
Measured current:
0 to 30 A (CTL-6-P-N)
0 to 100 A (CTL-12-S56-10L-N)
Input rating: Maximum current rating: 120 mA
Input impedance: Approx. 2.5 Ω
Performance:
Display accuracy
(at the ambient temperature 23 °
°°
°C ±
±±
± 2 °
°°
°C):
Thermocouple:
± (0.5 % of display value + 1 digit) or ± 3 °C [6 °F]
Whichever is greater
R and S input: 0 to 399 °C [0 to 799 °F]:
± 6 °C [12 °F]
B input: 0 to 399 °C [0 to 799 °F]:
Accuracy is not guaranteed.
RTD: ± (0.5 % of display value + 1 digit)
or ± 0.8 °C [1.6 °F]
whichever is greater
Voltage/Current: ± (0.5 % of span + 1 digit)