Instruction manual

IMNZC21-E1
3
3.2 Terminal Configuration
Power supply
Control output
Input
NO: Normally open
6
7
8
9
10
14
12
1
2
3
4
5
AC
24V
DC
100240V
AC
24V
7
6
7
6
7
6
L
N
+
L
N
CT input
Current
transformer
11
12
CT
TC input
+
TC
8
9
RTD input
A
B
B
RTD
8
9
10
C100
13
11
Alarm output
Relay contact
ALM1
ALM2
NO
NO
3
2
1
A
larm 2, Heater break
alarm or Control loop
break alarm
A
larm 1 or
Control loop
break alarm
OUT
T2
T1
G
3
5
4
Trigger for
triac drive
OUT
+
5
4
Voltage pulse/
Current
Relay contact
NO
OUT
4
5
Terminals which are not used according to
the controller type are all removed.
When control output is trigger output for triac
driving, the number of alarm output points
becomes 1.
Use the solderless terminal appropriate to
the screw size.
Screw size: M3 x 6
Recommended tightening torque:
0.4 N
m [4 kgf
cm]
Maximum allowance: 0.7 N
m [7 kgf
cm]
6.2 mm (0.24 inch) or less
Voltage/Current
+
8
9
Power supply
Control output
NO: Normally open
NC: Normally closed
W, A action types
Relay contact
F, D action types
NC
NO
OUT
6
7
8
C400, C410, C900
1
2
3
4
5
6
7
8
10
11
9
12
13
14
15
16
17
18
19
20
22
23
21
24
Ground
1
8.1 mm (0.32 inch) or less
Terminals which are not used according to the
controller type are all removed.
An example of the C900 is described here, the
same wiring examples also apply to C400/C410.
(Terminal numbers 17 to 24 are not provided for
C400/C410.)
Use the solderless terminal appropriate to the
screw size.
Screw size: M3 x 8
Recommended tightening torque:
0.4 N
m [4 kgf
cm]
Maximum allowance: 1.0 N
m [10 kgf
cm]
OUT
T2
T1
G
6
8
7
Trigger for
triac drive
OUT
+
8
7
Voltage pulse/
Current
Relay contact
NO
OUT2
NO
OUT1
5
6
7
8
OUT2
OUT1
+
+
5
6
7
8
TC input
+
TC
15
16
RTD input
B
B
A
RTD
14
15
16
Input
Current
transformer input
13
12
CT
Alarm output
100
240V
AC
24V
DC
24V
AC
3
3
2
3
2
L
N
+
L
N
Relay contact
ALM1
ALM2
NO
NO
11
10
9
A
larm 1 or
Control loop
break alarm
A
larm 2, Heater break
alarm or Control loop
break alarm
CT input
Voltage pulse/
Current
Voltage/Current
+
15
16
2
C700
1
2
3
4
5
6
7
10
8
11
12
13
14
15
16
18
19
17
20
6.2 mm (0.24 inch)
or less
8.1 mm (0.32 inch)
or less
Screw size: M3 x 6
Terminals Nos. 1 to 10
(Power terminals, Alarm
terminals and Out
p
ut terminals
)
Screw size: M3 x 8
Terminals Nos. 11 to 13
(Input terminals)
9
Power supply
Control output
NO: Normally open
NC: Normally closed
W, A action types
Relay contact
F, D action types
NC
NO
OUT
6
7
8
Ground
1
Terminals which are not used according to
the controller type are all removed.
Use the solderless terminal appropriate to the
screw size.
Recommended tightening torque:
0.4 N
m [4 kgf
cm]
Maximum allowance: 1.0 N
m [10 kgf
cm]
OUT
T2
T1
G
6
8
7
Trigger for
triac drive
OUT
+
8
7
Voltage pulse/
Current
Relay contact
NO
OUT2
NO
OUT1
5
6
7
8
OUT2
OUT1
+
+
5
6
7
8
100
240V
AC
24V
DC
24V
AC
3
3
2
2
3
2
L
N
+
L
N
Voltage pulse/
Current
TC input
+
TC
12
13
RTD input
B
B
A
RTD
11
12
13
Input
Current
transformer input
20
1
9
CT
Alarm output
Relay contact
ALM1
ALM2
NO
NO
10
9
8
A
larm 1 or
Control loop
break alarm
A
larm 2, Heater break
alarm or Control loop
break alarm
CT input
Voltage/Current
+
12
13
Specifications
Input:
Input type:
Thermocouple: K, J, R, S, B, E, T, N, PLII,
W5Re/W26Re, U, L
Input impedance: Approx. 1 M
RTD: Pt100, JPt100
Voltage: 0 to 5 V DC, 1 to 5 V DC
Input impedance: 250 k or more
Current: 0 to 20 mA DC, 4 to 20 mA DC
Input impedance: Approx. 250
Sampling cycle:
0.5 seconds
Input range:
See
Input range table
Control method:
PID control
ON/OFF, P, PI, or PD actions is available
Control output:
Relay contact output: 250 V AC, 3A (Resistive load)
Electrical life:
300,000 times or more (Rated load)
Voltage pulse output: 0/12 V DC
(Load resistance 600 or more)
Current output: 4 to 20 mA DC
(Load resistance 600 or less)
Trigger output (for triac driving):
Zero cross method for medium capacit
y
triac driving (100 A or less)
Load voltage used:
100 V AC line, 200 V AC line
Load used: Resistive load
Memory backup:
Backed up by Nonvolatile Memory
Number of write times:
Approx. 100,000 times
Data storage period:
Approx. 10 years
Power:
Power supply voltage:
85 to 264 V AC (Power supply voltage
range), 50/60 Hz
Rating: 100 to 240 V AC
21.6 to 26.4 V AC (Power supply
voltage range), 50/60 Hz
Rating: 24 V AC
21.6 to 26.4 V DC (Power supply
voltage range)
Rating: 24 V DC
Power consumption:
6 VA max. (at 100 V AC)
9 VA max. (at 240 V AC)
6 VA max. (at 24 V AC)
145 mA max. (at 24 V DC)
Weight:
C100: Approx. 170 g
C700: Approx. 250 g
C400/C410: Approx. 260 g
C900: Approx. 340 g
Alarm output:
Relay contact output:
250 V AC, 1A (Resistive load)
Electrical life: 50,000 times or more
(Rated load)
Heater break alarm function:
Measured current:
0 to 30 A (CTL-6-P-N)
0 to 100 A (CTL-12-S56-10L-N)
Input rating: Maximum current rating: 120 mA
Input impedance: Approx. 2.5
Performance:
Display accuracy
(at the ambient temperature 23 °
°°
°C ±
±±
± 2 °
°°
°C):
Thermocouple:
± (0.5 % of display value + 1 digit) or ± 3 °C [6 °F]
Whichever is greater
R and S input: 0 to 399 °C [0 to 799 °F]:
± 6 °C [12 °F]
B input: 0 to 399 °C [0 to 799 °F]:
Accuracy is not guaranteed.
RTD: ± (0.5 % of display value + 1 digit)
or ± 0.8 °C [1.6 °F]
whichever is greater
Voltage/Current: ± (0.5 % of span + 1 digit)