Installation Guide
> Dip Switch setting with control panel
Terminal
Resistance
8
4
2
1
1 2
3
4
5
6
Swi tch Set ting Swi tch Set ting
Addr ess
Addr ess
1
2
3
4
5
6
7
8
1 2
3
4
5
6
1 2
3
4
5
6
1 2
3
4
5
6
1 2
3
4
5
6
1 2
3
4
5
6
1 2
3
4
5
6
1 2
3
4
5
6
1 2
3
4
5
6
5
Working Principle
Number 1, 2, 3, 4 of the dip switch are used to set the address of RS485, 5 is the
reset switch, and 6 is the Terminal Resistance.
Number 5 is the reset switch: dial up and dial down. The machine will restart and
reset successfully
The right side figure shows the address number setting.
Number 6 switch is used to set the terminal resistance in RS485.
Communication: If the 485 communication wire is longer, than 100 meters, it is
needed to set the number 6 dip switch of the last reader to ON state, that is
parallel a terminal resistance of 120 ohm between 485+ and 485-.
BLACK
GND
12V
GND
485+
485-
PURPLE
YELLOW
BLACK
RED