User guide
1.6 SPECIFICATION
NPUT CHARACTERISTICS: R1M-6250P
l VOLTAGE: 90 ~ 264 VAC FULL RANGE
l FREQUENCY : 47 ~ 63 Hz
l INPUT CURRENT: 6.0 / 3.0 A FOR 115 / 230 VAC
l INRUSH CURRENT: 50A / 70A MAX. FOR 115 / 230 VAC PER POWER MODULE
OUTPUT CHARACTERISTICS:
OUTPUT CURRENT REGULATION OUTPUT
MIN.[A]
MAX.[A]
PEAK(A)
LOAD LINE
5V 3.0 25 ±
5%
±
1%
50mV
12V 2 16
±
5%
±
1%
120mV
-5V 0 0.5
±
10%
±
1%
150mV
-12V 0 0.5
±
10%
±
1%
150mV
3.3V 1.0 15
±
5%
±
1%
50mV
+5VSB 0.1 2.0
±
5%
±
1%
50mV
OUTPUT
VOLTAGE
RIPPLE & NOISE
MAX. [P-P]
REMARKS: TOTAL CURRENT OF +5V AND + 3.3V NOT EXCEED 28 A
TOTAL +5V AND 3.3V AND 12V POWER NOT EXCEED 232 W
. TEMPERATURE RANGE : OPERATING 0
0
C --- 40
0
C, STORAGE –20
0
C --- 80
0
C
l HOLD UP TIME: 16 ms MINIMUM AT FULL LOAD & 90 VAC INPUT VOLTAGE
l DIELECTRIC WITHSTAND: INPUT / OUTPUT 3000 VAC FOR 1 MINUTE
INPUT TO FRAME GROUND 1500 VAC FOR 1 MINUTE
l EFFICIENCY: 63% TYPICAL, AT FULL LOAD
l POWER GOOD SIGNAL: ON DELAY 100 ms TO 500 ms, OFF DELAY 1 ms
l OVER LOAD PROTECTION: 110 ~ 160% MAX.
OVER VOLTAGE PROTECTION:
+5V à 5.7V ~ 6.6V, 3.3V à 3.9 ~ 4.3V, 12V à 13.0 ~ 15.0V
. SHORT CIRCUIT PROTECTION : 5V,3.3V,12V,AUTO-RECOVERED:5VSB,-5V,-12V
l EMI NOISE FILTER: FCC CLASS B, CISPR22 CLASS B
l SAFETY: MEET UL 60950, CSA 22.2 NO/ 60950, TÜV EN 60950,CE IEC60950,CCC
GB4943-1995, GB9254-1998, GB17625.1-1998.
l REMOTE ON / OFF CONTROL
l FAULTY ALARM METHODS : LED, BUZZER, TTL SIGNAL
l HOT-SWAPPABLE / HOT-PLUGGABLE 1 + 1 REDUNDANCY FUNCTION
l BALANCE LOAD SHARING DESIGN
l REMOTE SENSING DESIGN
l ISOLATION: BUILT-IN IN THE POWER MODULE
l MEET IEC-1000-3-2 CLASS D ( ACTIVE PFC )
l DIMENSION: 40.5(H) X 180(W) X 260 (D) mm ;
l COOLING : TWO 40 mm DC FANS (ONE IN EACH MODULE)