Sheathing and Tape Brand Brochure

ZIP System
®
Performance
Water Resistance of Coatings
ASTM D 2247
(for 14 days)
Passed
Drainage Efciency ASTM E 2273 > 90%
Water Vapor Transmission ASTM E 96B
12-16 perms
(overlay)
Water Penetration ASTM E 331 Passed
Air Barrier Assembly
ASTM E 2357
at 75 Pa
0.037 L/(s∙m
2
)
Wind Driven Rain TAS-100 Passed 100mph
Accelerated Weathering ASTM G 154 Passed
Long term thermal resistance values of the foam were determined in accordance with
ASTM C 1289-02. The R-Value of 0.55 for 7/16" OSB was obtained from ASHRAE
Handbook, Fundamentals.
For SI: Inch = 25.4mm; 1 pound per foot (ppf) = 14.59 N/m.
1 Prescriptive bracing requirements with Douglas Fir-Larch Framing under the 2009 IRC.
2 Not approved for use as prescriptive wall bracing where the design wind speed is greater than 110mph.
3 Engineered shear wall requirements with Douglas Fir-Larch Framing under the 2015, 2012, and 2009 IBC.
4 For framing with other than Douglas Fir-Larch, the shear value above must be multiplied by the Specic Gravity Adjustment Factor = [1 - (0.50 - SG)], where SG=Specic Gravity
of the framing lumber in accordance with the ANSI/AWC NDS. This adjustment factor must not be greater than 1.
5 Type R-3 R-sheathing panels have a foam plastic insulation thickness of .5". Type R-6 R-sheathing panels have a foam plastic insulation thickness of 1". R-9 R-sheathing
panels have a foam plastic insulation thickness of 1.5". Type R-12 R-sheathing panels have a foam plastic insulation thickness of 2".
6 Fasteners must be common nails or equivalent, or staples, of a type generally used to attach wood sheathing.
7 The shearwalls must have a maximum height-to-width aspect ratio of 2:1.
8 This panel and fastening conguration is only applicable to the prescriptive bracing requirements under the 2015 IRC.
9. ZIP System R-sheathing used as the lateral resistance system in seismic zones C, D
0
, D
1
, D
2
and E should be designed in accordance to ER-482.
FASTENING REQUIREMENTS FOR PRESCRIPTIVE BRACING
1, 2
AND
ENGINEERED SHEAR WALL DESIGN
3
1", 1-1/2", 2", 2-1/2" ZIP System
®
R-sheathing
Panel Type
2
Total Thickness Panel Size Panel Count R-value Code Evaluation Report Air Barrier
R-3 1" 4' x 8' 32 3.6
ESR 3373
ASTM E 2178
<0.02 L/(s∙m
2
)
@ 75 Pa
ASTM E 2357
<0.2 L /(s∙m
2
)
@ 75 Pa
R-6 1-1/2" 4' x 8' 31 6.6
R-9 2" 4' x 8' 23 9.6
R-12 2-1/2" 4' x 8' 18 12.6
Foam Performance
Property Test Method Typical Results
Dimensional Stability ASTM D 2126 <2%
Compressive Strength ASTM D 1621 20 psi
Water Absorption
ASTM C 209
ASTM D 2842
<1%
<3.5%
Water Vapor Transmission ASTM E 96 <1.0 perm
Density ASTM D 1622 Nominal 2.0 pcf
Flame Spread ASTM E 84 40-60
Smoke Developed ASTM E 84 50-170
Tensile Strength ASTM D 1623 > 730 psf
Service Temperature -40°− 200°F
Framing
4
Fasteners Shear Values
ZIP System
®
R-sheathing Type
5
Nominal Stud
Spacing (min.)
Maximum Stud
Spacing (in.)
Fastener
Specications
6
Edge/Field
Spacing (in.)
Maximum
Penetration into
Framing (in.)
Allowable Seismic
Controlled Shear
Values
7, 9
(plf)
Allowable Wind
Controlled Shear
Values
7
(plf)
R-3 2-by-4 24 0.131" shank nails 4/12 1.5 245 343
R-3 2-by-4 24 0.131" shank nails 3/12 1.5 280 393
R-3 2-by-4 16
16ga staples, 7/16"
crown, 2" length
3/6 1.0 210 294
R-6 2-by-4 24 0.131" shank nails 4/12 1.5 230 322
R-6 2-by-4 24
15ga staples, 7/16"
crown, 2.5" length
3/6 1.0 NA
8
NA
R-6 2-by-4 24 0.131" shank nails 3/12 1.5 255 357
R-9 2-by-4 24 0.131" shank nails 3/12 1.5 240 336
R-12 2-by-4 24 0.131" shank nails 3/12 1.5 215 301
ER-482
9