Third Party Verification Claim

April 1, 2010
Mr. John Tomaini
J.T. Products, Inc.
P.O. Box 626
Warwick, NY 10990
RE: Report of Duct Leakage Test with Zip-Ez Duct Wrap & Flex Fasteners
Overview:
The purpose of this test was to determine if the Zip-Ez insulation fasteners
contribute to or cause excessive duct leakage when installed. The Zip-Ez
fastener consists of a conical plastic washer held in place with a coarse thread
sheet metal screw.
To conduct the test, a section of 12” x 12” x 8’ length of 16 gauge sheet metal
duct was fabricated. One end of this duct was closed with a sheet metal end cap.
All seams and end cap were sealed with duct mastic and allowed to dry for
several days.
A standard duct leakage test was conducted using a Minneapolis Duct Blaster.
The flow meter was an Energy Conservatory DG-700 Pressure and Flow Gauge.
The gauge was within calibrated specifications.
The duct blaster was connected to the open end of the 12” x 12” duct using the
square mounting plate held in place with UL-approved foil duct sealant tape and
a flex duct connection to the Duct Blast fan.
Duct leakage tests were conducted at various pressures before and after
installation of the Zip-Ez fasteners.

Summary of content (3 pages)