Technical data

TR440 12310-0702-04 Seite
5
/ 24 www.ziehl.de
4 Display and controls
1 Digital display (3 digits)
Display of sensor value
Display of error codes
Display of menu and configuration
mode
2 Right-hand decimal point
Off: The device is in the display
mode
Illuminated: The device is in the
menu mode
Flashes: The device is in the
configuration mode
3, 5 Up key / Down key (in display mode, normal state)
Change into the menu mode (see Operating instructions Point 8.3)
Press for 2 s: Displays min/max measurement of the selected sensor
Additionally pressing key set ≥ 2s deletes all min/max values
Press Up and Down ≥ 2s: EasySimulation, jumps into simulation mode for the sensors 1T
.. 3T (display 8S1-38)
4 Set/Reset key (in display mode, normal state)
Press briefly: Displays the next sensor (sensor LED illuminates)
Press for 2 s: Reset function, deletes a locked alarm
(=> [Delay time Alarm off] must have expired)
Press for 5 s: Displays the program number (e.g. 8PR38)
Press for 8 s: Displays the measurand (e.g. 8 °C8)
Press for 10 s: Displays the software version (e.g. 8-008)
6 LED (red) error
Illuminated: Sensor error in one sensor circuit or an internal
device fault has occurred
7 LEDs (yellow) sensors
Illuminated: Displays the sensor value belonging to the LED in the
digital display
Flashes: Sensor error in the corresponding sensor circuit
8 LEDs (red) alarm
Illuminated: Alarm (1-4) has occurred
Flashes quickly (1:4): [Delay time Alarm on] running
Flashes long (4:1): [Delay time Alarm off] running
Flashes uniformly (1:1): Ready for reset, reset with key
Press "SET/RESET" ≥ 2s
9 LEDs (yellow) relay state
Illuminated: The relay belonging to the LED is operating
Off: The relay belonging to the LED is released