Technical data
TR440 12310-0702-04 Seite
4
/ 24 www.ziehl.de
Program 1:
Program 2:
3 sensors in the windings:
3 sensors in the windings and 1 sensor in the
transformer core:
Fan/FAN (with cyclic test)
Advance warning 8alr8
Shutdown 8trp8
Malfunction (sensor error)
Fan/FAN (with cyclic test)
Advance warning (winding + core) 8alr8
Shutdown (winding + core) 8trp8
Malfunction (sensor error)
For the sensors in the windings and for the sensor
in the core, various limits can be set for each.
Program 3:
Program 4:
3 sensors in the windings and 1 sensor in the
transformer core:
3 sensors in the windings and 1 sensor in the
transformer core:
Fan/FAN (with cyclic test)
Advance warning (winding) / malfunction
combined 8alr8
Shutdown (winding) 8trp8
Shutdown (core) 8Cor8
Shutdown (core) 8Cor8
Advance warning (winding) 8alr8
Shutdown (winding) 8trp8
Malfunction (sensor error)
Alarm 2 simultaneously to reach the advance
warning temperature and the fault message.