ZIEHL industrie – elektronik GmbH + Co KG Daimlerstraße 13, D – 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers Grid- and Plant Protection updated: 140407 Sc Operating Manual TR440 - Transformer protection temperature relay TR440 12310-0702-04 Seite 1 / 24 www.ziehl.
Table of contents 1 Use and brief description ....................................................................................................................... 3 2 Overview of the functions ...................................................................................................................... 3 3 Connection diagram ............................................................................................................................... 3 4 Display and controls ..............
1 Use and brief description Temperature relay to protect transformers against excess temperature and to control a fan. The temperatures in the windings are monitored with three Pt 100 sensors. The core temperature can be monitored with a fourth sensor. The 4 alarms/output relays are used to control the fan, to signal an advance warning and to switch-off the transformer. Various programs facilitate using the alarm ideally for each application. Depending on the program, e.g.
Program 1: 3 sensors in the windings: Fan/FAN (with cyclic test) Advance warning 8alr8 Shutdown 8trp8 Malfunction (sensor error) Program 3: 3 sensors in the windings and 1 sensor in the transformer core: Fan/FAN (with cyclic test) Advance warning (winding) / malfunction combined 8alr8 Shutdown (winding) 8trp8 Shutdown (core) 8Cor8 Alarm 2 simultaneously to reach the advance warning temperature and the fault message.
4 Display and controls 1 Digital display (3 digits) Display of sensor value Display of error codes Display of menu and configuration mode 2 Right-hand decimal point Off: The device is in the display mode Illuminated: The device is in the menu mode Flashes: The device is in the configuration mode 3, 5 Up key / Down key (in display mode, normal state) Change into the menu mode (see Operating instructions Point 8.
5 Important information WARNING Hazardous electrical voltage! Can lead to electric shock and burns. Before starting work, switch plant and device voltage-free. The flawless and safe operation of a device requires that it is shipped and stored appropriately, professionally installed and put into operation and operated according to its intended use.
6 Programs 4 programs (Pr) can be selected in the factory version. Starting from these programs, it is especially simple to adapt the device to the application. First select the program that fits your application and then change the individual parameters! All parameters are reset with when switching the program to "factory settings" (see "Connection Diagram" and see "Factor Settings").
Start-up operation (commissioning) 8.1 General instructions on operating On the decimal point behind the last 7-segment display one can recognise the device operating mode. 8.
8.3 Menu mode Decimal point on Select the menu items for viewing the parameters Function keys Up and Down Press briefly: Select menu item; change into the display mode Function key Set/Reset Press briefly: Change into the configuration mode 8.
8.5 Short operating diagram [Program 1] Display mode Menu mode Configuration mode Stop bit: from Firmware -04 TR440 12310-0702-04 Seite 10 / 24 www.ziehl.
8.6 Short operating diagram [Program 2] Display mode Menu mode Configuration mode Stop bit: from Firmware -04 TR440 12310-0702-04 Seite 11 / 24 www.ziehl.
8.7 Short operating diagram [Program 3] Display mode Menu mode Configuration mode Stop bit: from Firmware -04 TR440 12310-0702-04 Seite 12 / 24 www.ziehl.
8.8 Short operating diagram [Program 4] Display mode Menu mode Configuration mode Stop bit: from Firmware -04 TR440 12310-0702-04 Seite 13 / 24 www.ziehl.
8.9 Overview of commissioning Must Can Overview X 8.10 Selection of program number X 8.11 Switch on device X 8.12 Configure the sensors X 8.13 Configure the alarms X 8.14 Configure the relay test on K1 X 8.15 Configure the Modbus RS 485 interface (option) X 8.16 Sensor simulation X 8.17 Code block 8.18 Tips on operating 8.19 Possible indications in display 8.10 Selection of program number Set the program number as described in Point [6. Programs]. 8.
8.13 Configure the alarms The following parameters are significant: Alarm value 8FAN.8 8ALR.8 8tRP.8 8Cor.8 Limits for the alarms. Dependent on the selected program, various alarm settings are possible(see short operating diagrams) Hysteresis 8H Reset value is calculated from the alarm value + hysteresis, e.g.: 90°C (limit) + -5°C (hysteresis) = 85°C (reset value) Alarm delay on 8dal.8 An alarm is suppressed for the set time (seconds) Alarm delay off 8dof.
Set the desired value with the Up and Down keys Press the Set key Display 8rel .8 / 8 r.8 (relay / parameter) flash alternately Set the desired value with the Up and Down keys Press the Set key Display 8FAN.8 Select the next alarm with the Down key (with the Up key to previous alarm or menu item) Configure the next alarm After the last alarm setting, change to the next menu item (relay test) with the Down key 8.
8.15 Configure the Modbus RS 485 interface (option) The following parameters are significant: 8bus.8 Modbus Modbus menu Device address 8Adr.8 Device address, can be set from 1 to 247 Baud rate 8bd .8 Baud rate, 9600 8 9.6.8 or 19200 819.2.8 Parity 8par.8 Parity bit: 8evn.8, 8odd.8, 8 no.8 (even, odd, none) Stop 8StP.8 Stop bit: 8 1.8 / 8 2.8 (1 / 2) (-> from Firmware -04) Adjustment process: Select the menu item with the Up/Down key until … Display 8bus.8 Press the Set key Display 8Adr.
8.17 Code block Here, the set parameters can be protected by activating a code block. The device acknowledges an incorrect entry with 8Err8 (flashes three times). Select the menu item with the Up/Down key until … Display 8Cod.8 Press the Set key Display 8Pin.8 / 8 0.8 (pin / pin code) flash alternately Use the Up and Down keys to set the saved pin code (factory setting is 8504.8) Press the Set key Set the desired code block using the Up and Down keys: o 8off.
8.
Simulation, menu mode/configuration mode 8Si .8 Simulation Sensor to be simulated, Sensors S1...S3 Sensor S4 8S1-3.8 / 8S 4.8 Code block, menu mode/configuration mode 8Cod.8 Code block 8Pin.8 Pin code 8on .8 / 8off.8 Code block on / off 9 Factory settings When changing programs (operating instructions point Programs), all parameters are reset to the factory settings.
Alarm Relay K4 Relay test Modbus (Option) Alarm name 8Err8 8Err8 8COR8 8Err8 Limit --- --- 81708 --- --- --- 8 -58 --- 8dal8 (Delay Alarm) --- --- 8 08 --- 8dof8 (Delay Alarm off) --- --- 8 08 --- 8rel8 (Relay function) 8 8 8 a8 8don8 81688 81688 81688 8off8 8dof8 80.208 80.208 80.208 8 0.08 8adr8 8 8 8 8 8bd 8 8 9.68 8 9.68 8 9.68 8 9.
The device cannot be programmed (configured) Cause Remedy Code block The code block provides protection against unauthorised manipulation on the device. When the code block is active, the parameters cannot be change. The pin can be set by the user.
12 Technical data Control voltage Us Limits Sensor connection Measuring range Sensor resistance + line res.
Housing Dimensions (W x H x D) Line connection single strand Finely stranded with wire end sleeve Housing internal protection Terminal strip protection type Mounting Panel monitoring housing SE 2 96 x 96 x 80 mm per 1 x 2.5 mm2 per 1 x 2.5 mm2 Front panel IP 54 (with seal), rear IP 20 IP 20 Panel mounting, Cut-out 91+0.7 x 91+0.7 mm approx. 310 g Weight The right to make technical changes is reserved. 13 Mounting type SE 2 Dimensions in mm Panel opening 91+0.7 x 91+0.