OPERATION DETAILS
2
40
60
1
120
180
3
74.0Hz
80.0Hz
4
32.0Hz
32.0Hz
+3.0
29˚C
33˚C
15˚C
MAX
3
MAX
3
MIN4
MIN4
+5.0
0
Hz
Super
low
Frequency of
compressor
Designate Fan blow
Low Low
Low Super low
Designated
Fan blow
Designated
temperature
Room temperature
Stop
Temperature,
indoor heat
exchanger
Indoor fan
20sec.
S 1731
S 1735
HEATING MODE OPERATION
The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for 1 seconds and the room temperature becomes 5.0°C higher than it was set.
The compressor will re-start when room temperature becomes 3.0°C higher than it was set.
The operational frequency will be set every 2 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the
set temperature on one end and the deviation factor at the time of previous setting on another.
Model