Service manual

4
61
6
. All wiring must comply with local and national electrical standards and codes and be installed by qua-
lified and skilled electricians.
7. An individual branch circuit and single receptacle used only for this air conditioner must be available.
See the following table for suggested wire sizes and fuse specifications:
Connect the cable to the indoor unit
1. Indoor/Outdoor connection cable should be H07RN-F type.
2. Remove the panel and Screw, then remove the window cover.
3. Connect cables according to their marks to terminals.
4. Wrap those cables not connected with terminals with insulation tapes, so that they will not touch any
electrical components.
5. Fit the power cord clamp.
G
ATTENTION
Always make sur
e that the electrical connection cables fr
om indoor to outdoor unit ar
e cor
r
ect fitted,
e.g. when a green electrical line is fitted to clamp with code “L” in the indoor unit the other end of
that same green electrical line should be connected to clamp with code “L” on the outdoor unit.
1
0
m
m
4
0
m
m
G
NOTE!
The supply voltage should be consistent with the rated voltage
of the air conditioner.
Model Power supply
Input Rated Current
(Switch/Fuse)
Power Cord Size
<
3.5 kW
220-240V~50Hz
10A 1.0/1.5mm
2
3.5 kW
model
< 6.1 kW
16A 1.5mm
2
6.1 kW model
32A / 25A
2.5mm
2
Panel
Window cover
Cord clamp
To outdoor unit
6.1 kW models
Code wire
Or
Terminal block of indoor unit
To outdoor unit
Panel
Window cover
To outdoor unit
Terminal block of indoor unit
> 6.1 kW models
Or
Cord clamp