Specifications
A-6 System Standards and Specifications
Model No.
Running Head
Ambient refers to conditions at a location 1.5 m (59 in) above the floor and 400 mm (15.8 in)
in front of the equipment. Short-term refers to a period of not more than 96 consecutive hours
and a total of not more than 15 days in 1year. This refers to a total of 360 hours in any given
year, but, no more than 15 occurrences during that 1 year period.
A.3.3.2 Altitude
As per GR-63-CORE R4-8. Functional within the limits specified in the table above when
installed at elevations between 60 m (197 ft.) below sea level and 1800 m (5905 ft.) above sea
level. As per O4-10. Functional within the limits specified in the table above when installed
at elevations between 1800 m (5905 ft.) and 4000 m (13,123 ft.) above sea level.
A.3.3.3 Airflow
The IMACS-200 includes two fans. The fans are temperature controlled to automatically turn
on and off as needed.
A.3.3.4 Fire Resistance
As per GR-63-CORE Section 4.2.2.2 Shelf-Level Fire-Resistance Criteria R4-19 for
Firespread R4-20, Fire Propagation R4-21, O4-22 and O4-23.
A.3.4 Equipment Handling
A.3.4.1 Packaged Equipment Shock Criteria
As per GR-63-CORE Section 4.3.1.1 for category A containers, R4-41.
A.3.4.2 Unpackaged Equipment Shock Criteria
As per GR-63-CORE Section 4.3.2 R4-43.
A.3.5 Earthquake, Office Vibration and Transportation Vibration
A.3.5.1 Earthquake
To Zone 4 Profile (Zone 4 is most severe so equipment also meets Zones 0, 1, 2, and 3 criteria).
Physical performance as per GR-63-CORE Section 4.4.1.2 R4-44. Functional performance as
per GR-63-CORE Section 4.4.1.2 R4-48 and R4-49.