7 APPENDIX 24V AC WIRE GAUGE AND
TRANSMISSION DISTANCE RELATIONSHIP SHEET
It is the recommended transmission distance when the cable diameter is fixed and the 24V AC
power consumption is below 10%. For the AC device, the max permission voltage power
consumption is 10%. For example, when a device of rated power 20W installed 141 inches (42m)
from the transformer, then the min cable diameter is 0.8000mm.
mm
Feetm
w
0.8000
1.000
1.250
2.000
5
488.52148.90
763.31232.66
1192.67363.53
3053.25930.63
10
244.2674.45
381.66116.33
596.34181.76
1526.62465.31
15
162.8449.63
254.4477.55
397.56121.18
1017.75310.21
20
122.1337.23
190.8358.16
298.1790.88
763.31232.66
25
97.7029.78
152.6646.53
238.5372.71
610.65186.13
30
81.4224.82
127.2238.78
198.7860.59
508.87155.10
35
69.7921.27
109.0433.24
170.3851.93
436.18132.95
40
61.0618.61
95.4129.08
149.0845.44
381.66116.33
45
54.2816.54
84.8125.85
132.5240.39
339.25103.40
50
48.8514.89
76.3323.27
119.2736.35
305.3293.06
55
44.4113.54
69.3921.15
108.4233.05
277.5784.60
60
40.7112.41
63.6119.39
99.3930.29
254.4477.55
65
37.5811.45
58.7217.90
91.7427.96
234.8771.59
70
34.8910.64
54.5216.62
85.1925.97
218.0966.47
75
32.579.93
50.8915.51
79.5124.24
203.5562.04
80
30.539.31
47.7114.54
74.5422.72
190.8358.16
85
28.748.76
44.9013.69
70.1621.38
179.6054.74
90
27.148.27
42.4112.93
66.2620.20
169.6251.70
95
25.717.84
40.1712.25
62.7719.13
160.7048.98
100
24.437.45
38.1711.63
59.6318.18
152.6646.53