Instruction manual

Operation
14 025-9209
Slot No.
There are up to 16 slots to configure.
Source Address
Input the address of the transmitting unit.
Destination Address
Input the address of the unit that the transmitting unit is trying to reach.
Replacement Source Address
Input the new address of the transmitting unit.
Replacement Destination Address
Input the new destination address of the transmitting unit.
Next slot
Go to the next slot.
Exit
This selection will take the user back to the main menu.
Example
Controller Unit
#0
RTU
#5
RTU
#150
If RTU #150 is out of range of Controller Unit #0, but RTU #5 is in range of both Controller
Unit #0 and RTU #150, we would configure RTU #5 as the store and forward unit with the
values shown in Table 5.
Table 5. Store and Forward Address Assignments
Parameter Value Parameter Value
SLOT # 1 Source Address 0 SLOT # 2 Source Address 150
Destination Address 10 Destination Address 5
Replacement Source Address 5 Replacement Source Address 10
Replacement Destination Address 150 Replacement Destination Address 0