INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Approved Document No: GLT-201-7-2 Issue: 1.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Contents 1. FIRE ALARM CONTROL PANEL SAFETY ISSUES ........................................................................ 2 2. THE PURPOSE OF A FIRE ALARM SYSTEM ................................................................................. 2 3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, INCLUDING THE FACP & ITS INTEGRAL PSE ........................................................................................................
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 1. FIRE ALARM CONTROL PANEL SAFETY ISSUES There is no need to open this fire alarm during normal operation. Any work carried out on this system must be performed by a competent person who is familiar with this type of system. This equipment will operate safely provided it has been installed correctly in compliance with the Installation Manual. It is recommended that the system is serviced frequently.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, INCLUDING THE FACP & ITS INTEGRAL PSE According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings (BS5839: Pt 1: 2002), the owner or person having control of the premises should appoint a responsible person to oversee the effective operation of the Fire Alarm System (Clause 47.1).
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 4. PANEL INDICATIONS & CONTROLS Two levels of control are available to the User(s) of this Fire Alarm Panel. 4.1 GENERAL CONTROLS When the Panel is in its Normal state, the indicator lights on the front of the enclosure give a comprehensive overview of the System’s current status. Any Fire and Fault conditions are clearly displayed, and any disablements highlighted.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 4.3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING Use the table below to determine the condition of the panel. LEDs LIT POWER LED CONDITION CONSTANT GREEN PANEL STATUS The panel is supplied with power, and has no faults / fires (System Normal) GEN FLT ONLY FLASHING YELLOW GEN FLT & SUPPLY FLT FLASHING YELLOW FLASHING YELLOW There is a problem with either the mains supply or the battery backup.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 5. THE FIRE CONDITION 5.1 HOW THE INFINITY 8 INDICATES AN ALARM When the Infinity 8 Fire Alarm Panel is set into alarm by a Detector or Manual Call Point located in a zone that is not already in alarm it will: - Light the General Fire LED and appropriate Zone Fire LED(s) on the front of its enclosure Sound Internal buzzer Start the Alarm Sounder and Auxiliary output, (provided there is no Delay set on the sounders).
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK (e.g. cooking smoke), the smoke will have to be cleared from the room before the panel can be reset. Reset the panel by pressing the after the sounders and panel buzzer have been silenced. If the call point is still active, or the detector is still smoky, this will cause another alarm straight after the panel is reset, so will set off alarm bells again. 6. THE FAULT CONDITION 6.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK System Fault The System Fault LED and Gen fault lights when the Panel’s micro-processor has Reset, typically after excessive electrical interference, or if the contents of its memory have been corrupted. This fault can only be cleared by turning the key switch from off position to control enable position and then back to the off position again.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 7. DISABLEMENTS 7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM. Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is possible for the user to disable that zone during the risk period and then enable it again afterwards.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 8. USING SOUNDER DELAYS 8.1 WHAT IS A SOUNDER DELAY In certain circumstances it may be desirable to have a delay between the panel detecting a fire, and starting its external sounders, to allow the responsible person to check the cause of the alarm, to stop building evacuation by an obvious false alarm. If the cause of the Alarm is found to be a true fire hazard, the Delay can be overridden and the Alarm Sounders activated immediately.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 9 ZONE TEST 9.1 Why use Zone Test To aid commissioning and assist routine maintenance checks, a non-latching ‘One Man Test’ facility is available. When a detector or manual call point is triggered on any zone in test, the alarm sounders operate for approximately 5 seconds on and 5 seconds off.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 10.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 11. FIRE ALARM LOG BOOK It is recommended that this LOG BOOK section of the Manual be maintained by the responsible person(s) on site, who should ensure every event is properly recorded (including fire alarm conditions, failures, tests, temporary disconnections, disablements, enablement’s, dates of installing engineers’ visits together with a note of any outstanding work or panel conditions). This LOG BOOK must be available for inspection at all times.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK MAINTENANCE WORK DATE TIME ZONE / LOCATION REASON FOR WORK Approved Document No: GLT-201-7-2 Issue: 1.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FALSE ALARMS DATE TIME ZONE / LOCATION CAUSE (IF KNOWN) OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED (YES/NO) Approved Document No: GLT-201-7-2 Issue: 1.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME ZONE / LOCATION DETAILS OF EVENT (INCLUDING CAUSE IF KNOWN) Approved Document No: GLT-201-7-2 Issue: 1.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 12 COMMISSIONING THE SYSTEM, INCLUDING P.S.E. The commissioning of this fire alarm system should be performed by a qualified commissioning engineer, who has an understanding of sections 2,3,& 4 of BS5839 pt 1:2002 (i.e. Design considerations, Limitations of false alarms, Installation recommendations) The system layout drawing should be checked for accuracy & stored in a safe place, accessible to any fire officer.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Design Certificate (Page 1 of 2) Certificate of DESIGN for the Infinity 8 Fire Alarm System installed at: ADDRESS: I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the design of the fire alarm system, particulars of which are set out below, CERTIFY that the said design for which I/we have been responsible complies to the best of my/our knowledge and belief with the recommendations of section 2 of BS 5839-1:2
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Design Certificate (Page 2 of 2) Measures incorporated to limit false alarms. Account has to be taken of the guidance contained in section 3 of BS 5839-1: 2002 and, more specifically (tick as appropriate): The System is manual.
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Installation Certificate Certificate of INSTALLATION for the Infinity 8 Fire Alarm System installed at: ADDRESS: I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the installation of the fire alarm system, particulars of which are set out below, CERTIFY that the said installation for which I/we have been responsible complies to the best of my/our knowledge and belief with the specifications described below, and
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Commissioning Certificate Certificate of COMMISSIONING for the Infinity 8 Fire Alarm System installed at: ADDRESS: I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the commissioning of the fire alarm system, particulars of which are set out below, CERTIFY that the said work for which I/we have been responsible complies to the best of my/our knowledge and belief with the recommendations of Clause 39 of BS5839-1:
INFINITY 8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Acceptance Certificate Certificate of ACCEPTANCE for the Infinity 8 Fire Alarm System installed at: ADDRESS: I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the acceptance of the fire alarm system, particulars of which are set out below, ACCEPT the system on behalf of: Name (Block Letters): Signature: For & on behalf of: Address Position: Date: The extent of liability of the signatory is limited to the sys