INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH ‘ID’ TECHNOLOGY INSTALLATION MANUAL Approved Document No: GLT-211-7-1 Issue 1.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 CONTENTS 1.SAFETY INFORMATION ....................................................................................................................................... 3 1.1 Installation Information .............................................................................................................................. 3 1.2 Safety Precautions during Normal Operation of Panel .........................................
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 15 VIEWING PANEL INFORMATION ..................................................................................................................... 24 15.1 Menu Structure ....................................................................................................................................... 24 15.2 Viewing device status.........................................................................................
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 1.SAFETY INFORMATION WARNING: Read this section completely before commencing installation. 1.1 Installation Information THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED This equipment must be installed and maintained by a qualified and technically experienced person. This C.I.E. must be wired to a fused spur rated at 3A.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 2. PRODUCT DESIGN INFORMATION 2.1 Fire Alarm Control Section The Infinity ID2 Fire Alarm Control and Indicating Equipment (CIE) Has been designed to EN54-2:1998 A1 + A2 - Fire Detection & Fire Alarm Systems – Control & Indicating Equipment As well as meeting the requirements of EN54-2:1998 A1 + A2, the Infinity ID2 also has the following options with requirements:Clause 7.8 Clause 7.12 Clause 8.3 Clause 9.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 3.0 Panel description & design concept The Infinity ID2 is an eight zone intelligent fire alarm control panel designed to EN54 part 2 & 4. The Infinity ID2 has been designed to use zone powered sounders but also has 2 conventional sounder circuits. all sounders on an Infinity ID2 panel will activate on any alarm.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 4 USING THIS MANUAL It is beyond the scope of this manual to teach to teach the user all the intricacies of fire alarm system design. If in doubt about what is required, read BS 5839: Pt 1: 2002 “Fire Detection and Alarm Systems for buildings (UK Code of Practice for System Design, Installation, commissioning and maintenance)” available from the BSI, or at your local reference library.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 5 DESIGNING A SYSTEM This manual is not designed to teach Fire Alarm System design. It is assumed that the System has been designed by a competent person, and that the installer has an understanding of Fire Alarm System components and their use. We strongly recommend consultation with a suitably qualified, competent person regarding the design of the Fire Alarm System.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 6. INSTALLING THE SYSTEM 6.1 Considerations before Installation 6.1.1 MOUNTING THE CONTROL PANEL The control panel should be installed in accordance with the following recommendations: The panel should be close to the main entrance of the building, so that it can be viewed by any firefighting personnel entering the building. It should be fitted to a sturdy wall that will not flex unnecessarily.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 6.2 First Fix 6.2.1 MOUNTING THE FIRE ALARM PANEL The Infinity ID2 comes with many cable entry holes. If another entry hole is required, it is strongly recommended that the, the termination PCBs should be removed and stored in a safe place. This would also help while fixing the back box to the wall. 6.2.2 FIXING THE BACK BOX TO THE WALL Figure 2: Plan view inside the enclosure without PCBs.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 6.2.4 CONNECTING THE MAINS POWER Figure 3: Power Supply PCB layout and Mains connection details 2 The panel should be connected to 220-240V AC by a 3A rated spur to the fuse box with 1mm 2 to 2.5mm 3-core cable. Nothing else should be connected to this supply. The cable should be fire resistant. Having entered the panel via the cable gland, the mains cable should be passed twice through the provided ferrite.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 6.2.5 CONNECTING THE BATTERIES Figure 4: Battery location and connection details Although there are many sizes of suitable battery, the sizes we usually recommend for the INFINITY ID2 are 12V 3.4Ah, To calculate the exact requirement, use the equation in section 20.1, STANDBY BATTERY CALCULATIONS The two batteries are wired in series to give 24 Volts. Connect the –ve of Battery 1 to the black battery charger lead.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 7 ZONE WIRING The Infinity ID2 can be wired with up to 8 separate radial circuits each with 15 devices per circuit. It may also be wired as a single loop. Each termination is identified with on the terminal labels. The Earthing of the cable screens should be as shown in Fig 6. Approved Document No: GLT-211-7-1 Issue 1.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 7.1 Specific device wiring instructions All products will come with their own wiring instructions. This should be used when connecting a product. But as a general guideline, here are the connection details of most Zeta Addressable products.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 7.3 Setting the device zone & ID (detectors, call points & sounders) All devices will need to have their zone & ID switches set as described below. Switch 8 will depend on the type of the device. Zone setting Zone Number Switch 5 Switch 6 1 ON ON 2 OFF ON 3 ON OFF 4 OFF OFF 5 ON ON 6 OFF ON 7 ON OFF 8 OFF OFF Select the zone the device is fitted to (1 to 8). Each item on a zone has the same zone setting.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 8 SOUNDERS The Infinity ID2 has two conventional sounder circuits on board. 9. AUXILIARY OUTPUTS 9.1 Auxiliary output wiring Auxiliary Fire Relay (AUX): This is a SELV volt free relay that operates in the alarm condition. It can be connected to emergency lights, local fire fighting equipment such as sprinkler systems, magnetic door holders, air conditioning shut off, etc.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 10. FIELD DEVICE TERMINATION 10.1 Terminating the wiring Figure 6: Cable connections All cables entering the enclosure should have cable glands, which will prevent unwanted openings in the enclosure. The Zone circuits should be connected to the appropriate connector block on the Termination PCB.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 11 OTHER CONNECTIONS 11.1 Repeater connection The Infinity ID2 has an RS485 connection for a serial repeater. The repeaters has full control. Up to 3 repeater can be powered from the Aux 24V DC output on the panel. If 4 or more are to be connected, then they must be powered from external 24V power supplies. The panel supports up to 8 repeaters.
INFINITY ID2 INSTALLATION MANUAL. 12. CONFIGURING THE INFINITY ID2 FIRE ALARM PANEL 12.1 Configuring the Zones Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 Infinity ID2/8 Zone Fire Alarm Panel System Normal 24-09-2012 09:35 12.1.1 FROM A BLANK ID2 PANEL Devices Found 1. After the system has been installed, and the cabling checked and the addresses of each device set, connect the zone cables to the CIE termination PCB (connection 1-8 as shown in Section 21.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 12.3 Labelling the Zones 1. To add a Zone label, go to engineer menu 1 and select option 2 Panel / Zone Text. Select option 1 to enter the panel name or customer name Select option 2 to enter the zone text (i.e. ground floor) Panel / Zone Text 1: Panel 2: Zones 2. Press enter when the label has been entered. Press Next to edit the next zone. NOTE: For many installations, only these configuration steps are required.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 12.9 CHANGING INPUT/OUTPUT INTERFACE RESPONSE 12.9.1 DEFAULT SETTING To change the DEFAULT interface response, select option 2 in the Alarm operation menu.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 12.10 Setting the LCD language From Engineer menu 2, Select Misc (option 6) Then from the Misc Settings menu, select option 1 (Language) Pressing Prev / Next will scroll through the available languages.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 13 ALARM VERIFICATION The ID2 includes an option to use alarm verification. It is intended for use in apartments, and similar buildings, where it is desirable that an alarm from one apartment (or area) would need to be confirmed before the whole system goes into alarm. 13.1 How Alarm Verification Works The verification function works as follows:1. 2. 3. 4. 5.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 14 RESTORING THE PANELS DEFAULT SETTINGS Because the ID2 allows several configuration changes, we have also included an option to reset the panel back to its default operation. From Engineer Menu 2, Select Option 6 (Misc). Then from the System Menu, Select option 6 (Reset).
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 15 VIEWING PANEL INFORMATION 15.1 Menu Structure To help locate the different features available, the menu structure of the Infinity ID2 panel is shown here.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 15.2 Viewing device status On the ID2, all Zone devices can be viewed from Main Menu, or viewed & edited from Engineer Menu 1.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 15.4 Using the event log The ID2 has a 1000 entry event log. In the event of the log being full, it will wrap around, and overwrite the earliest entries. The event log can be viewed through Configuration Menu 1 by selecting Option 3 - View Event Log. The screen prompts for which events to display: Alarms, Faults, System or All.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 16. THE FIRE ALARM CONDITION 16.1 Viewing a fire alarm event The way the ID2 panel shows fire alarm information has been changed slightly from previous versions of the panel. The LCD screen text has been altered to show the first & last zone entering the alarm condition. For Example, a first alarm on a system will bring up the display: This Means there is a fire alarm condition.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 17. DISABLEMENT On the Simplicity, there are 2 disablement options. A whole zone of devices can be disabled, or an individual device in a zone can be disabled. Both types of disablement can be used at the same time if required. Note that when there is any type of disablement present, line 3 of the “System Normal” screen will show “Disablements Present”.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 17.3 Device disablement The ID2 panel can also disable individual devices (detector, call point, sounder or interface). To do this, enter ENGINEER MENU 1 and select ID DEVICE. Select the required device, them press GENERAL DISABLEMENT button. The Device label now flashes between the programmed label and Device Disabled. The general disablement LED will also be lit. This device is now disabled.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 18. TEST MODE 18.1 Why use test mode To aid commissioning and assist routine maintenance check, a silent, non-latching ‘one man test’ facility is available. When a detector or manual call point is triggered on any zone in Test, the Device will light it`s LED, When the smoke has cleared, or the call point has been reset, the LED will turn out.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 19. GENERAL FAULT FINDING On the ID2 panel, Faults are divided into 2 types, “Faults” and “Device Faults”. Device Faults are any fault associated with a particular address on the loop. Faults are everything else, EG , power supply etc. In the event of multiple faults, the Faults are grouped together first, followed by the device faults. Next button will scroll to next fault. 19.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 19.4 Supply faults 19.5 Earth faults An EARTH fault indicates that something is shorting to earth (usually through the cable screen). Disconnect the earth screens one at a time to determine the problem line.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 20. STANDBY BATTERY REQUIREMENTS 20.1 Standby battery calculation In order to calculate the standby battery size required, the following formula can be used:Battery Size (Standby time in Amp Hours) = 1.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 21. PCB TERMINATION CONNECTIONS. Connection No 1- 8 9 10 11 12 13 14 &15 16 17 18 19 Description Zone 1- 8 Sounder circuit 1 Sounder circuit 2 Fault Relay Fire Relay RS485 RS232 Aux Power Supply Battery Connections Thermistor 24VDC Input Approved Document No: GLT-211-7-1 Issue 1.
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624 22 SPECIFICATIONS 22.1 Enclosure specifications DESCRIPTION VALUE ENCLOSURE SIZE TOP CABLE ENTRIES 364 x 302 x 38 mm 15 x 19mm DIA ENTRIES 22.