Operating instructions

Page 12
CONTINUED FRAMING AND INSTALLATION
FLOOR PROTECTOR OR FINISHED HEARTH EXTENSION FLAT ON THE FLOOR
You must use a non-combustible material or a UL listed floor protector R-Value 0.6 .( SEE FLOOR
PROTECTION Page 8) All the way against front of cabinet and a minimum of 16" in front of stove feed
door opening and 47 1/2" the width of the cabinet (See Figure 12)
Construct the hearth extension (floor protector or finished hearth) out of non-combustible inorganic
building materials as follows:
a. The hearth extension must extend 16" from the stove feed door opening and against front of
80ZC cabinet. (See Figure 12).
b. The hearth extension width must be at least 47 1/2". (See Figure 12).
c. The hearth extension must be made of brick 2” thick or a listed “Floor Protector” or “Hearth
Extension” with R- value of: R=0.6 , or a hearth extension made of non-combustible inorganic
material with a K * factor of K=2.5 BTU ( (HR)(ft
2
)(F/in.) (See Page 8)
FLOOR PROTECTOR OR FINISH HEARTH EXTENSION
47 1/2”
16”
FIGURE 12
WARNING: Install the floor protector or finished hearth extension only as specified. The hearth
extension must be a minimum of 16" in front of the stove feed door opening and must be 47 1/2" wide
minimum. NOTE: Be sure to place safety shield under 80ZC and hearth protector or finished
hearth.
NOTE: No floor protector or finished hearth extension is needed directly under the Model 80ZC Cabi-
net, only the safety shield .