3.10 Changing the system date and time – all access levels
To set the date and time, press ‘MENU’, enter the correct password, select ‘1-Setup’, ‘1- Time & Date’. Use the ←and→ keys to
navigate to the value to change and the ↑ or ↓ keys to select the desired value. Press ‘ENTER’ to accept or ‘CANCEL’ to exit. The Zerio
Plus panel automatically adjusts the clock for daylight savings. Should complete power be lost the panel will revert the time back to the
default of 01/01/2011 12:00:00
Time: 12:29:00
Date: 01-01-2011
ENTER to save
3.11 Isolating a Zone – all access levels
If a zone is isolated the system will not display any fire or fault events for devices located in the zone. This includes any call point
activations.
Press ‘MENU’, enter the correct password, select ‘2-Disable/Enable’, select ‘1-Disable’, select ‘1-Disable Zone’. Using the ↑ or ↓ keys,
select the zone number to be disabled and press the ‘→’ key. Select the timeout (in hours) followed by the ‘→’ key. Finally, as indicated
on the display, press ‘ENTER’ to save the change. After this time has expired the isolated zone(s) will be automatically enabled. Press
‘ENTER’ to confirm the change (or ‘Cancel’ to exit without changing). The ‘Disablements’ LED will be illuminated. If more zones need
to be isolated press ‘ENTER’ again, or press ‘CANCEL’ to exit.
Select Zone 01↕ Timeout (hours) 01↕ Press ENTER to
Disable Zone 01
Use ← → keys Use ← → keys
To view which zones are disabled, select the appropriate ENABLE operation detailed below. Only the previously disabled zones can be
selected to be re-enabled. If no changes are required, press CANCEL.
3.12 Isolate a Device – all access levels
Once a device is isolated the system will ignore any fire or fault event from that device.
Press ‘MENU’ and enter a valid password. Select ‘2-Disable/Enable’, select ‘1-Disable’, select ‘2-Disable Device’. Using the ↑ or ↓
keys select the device number to be disabled and press the ‘→’ key. Select the timeout (in hours) followed by the ‘→’ key. Finally, as
indicated on the display, press ‘ENTER’ to save the change. After this time has expired the device that was isolated will automatically be
enabled. Press ‘ENTER’ to confirm the change (or ‘Cancel’ to exit without changing). The ‘Disablements’ LED will be illuminated. If
more devices are to be isolated press ‘ENTER’ again, or press ‘CANCEL’ to exit.
Select Device 01↕
SMOKE/SOUNDER Timeout (hours) 01↕ Press ENTER to
Disable Device 01
Use ← → keys Use ← → keys
To view which devices or zones are disabled select the appropriate ENABLE operation detailed below. Only the previously disabled
devices or zones can be selected to be re-enabled.
3.13 Enable a Zone – all access levels
To enable a previously isolated zone, press ‘MENU’ and enter a valid password. Select ‘2-Disable/Enable’, select ‘2-Enable’, select ‘1-
Enable Zone’. Using the ↑ or ↓ keys select the zone number to be enabled and press ‘ENTER’. To enable more zones press ‘ENTER’, or
‘CANCEL’ to exit. If all zones have been enabled ‘No Zones to enable’ will be displayed. If a previously disabled zone is enabled, and
no other ‘Disablement’ conditions exist such as an isolated device/zone, then the ‘Disablements’ LED will extinguish.
Select Zone 01↕ Press ENTER to
enable Zone
Use ← → keys