User manual
Version ZerioPlusI&OM_V1.01
EDA-Z5008 & Z5020 - Installation and Operation Manual
Electro-Detectors Page 13
Callpoint Override – Commissioning user only
When set to YES, callpoints will cause an alarm and sounders will sound if operated in Test Mode. When set to NO, callpoints will not
cause sounders to sound if operated in Test Mode. With YES selected, the service engineer can perform a silent system test for detectors
while leaving the callpoints active.
Sound Area – Commissioning user only
Setting this to zero will sound all sounders providing the sounder option is on. By selecting a specific sound area a certain group of
sounders can be operated that are programmed to this area.
This is useful so that during testing, a specific group of sounders (or single sounder) can be set of after each activation. Each test would
only operate this sounder provided it was programmed to a unique sounder area.
Fire Relay– Advanced, Service and Commissioning users only
The fire relay inside the panel is often used as a way of triggering a link to the fire brigade or to an alarm monitoring station If this relay
is required to be disabled, this parameter should be set to OFF. Always follow the procedure outlined by the system installer.
Timeout– Advanced, Service and Commissioning users only
This is the amount of time before the system will automatically exit test mode operation. This should be set slightly longer than the test
should take. It can be set in 1 hour intervals and is selected using the cursor keys. A maximum of 48 hours can be set.
After setting the timeout value, the option is given to press ‘ENTER’ to enable Test Mode. Alternatively, the ‘←’ key can be operated to
go back through the parameters and make any changes, or ‘CANCEL’ can be pressed to abort any changes
Press ENTER to
enable Test Mode
Use ← Key
After entering Test Mode, the ‘Test Mode’ LED will illuminate, and the panel will give the option to save the test mode setting for quick
set-up in future. If unsure of the saved settings, select NO and then ENTER.
Test Mode enabled
Save Test Settings
YES↕
ENTER to continue
Devices that require testing should now be set into a fire condition and the details on the screen checked. Care should be taken to ensure
the correct devices are tested as failure to do this could result in all the bells sounding.
Once the tests are complete and the user is satisfied that everything functioned correctly, the test mode should be disabled. If this
procedure is forgotten the test mode will automatically time out after the selected period.
4.5 Disable Test Mode– Advanced, Service and Commissioning users only.
Press ‘MENU’, and enter a valid password . Select ‘4-Test Modes’ then ‘2-Disable Test’ Press ‘ENTER’ to disable test. The ‘Test Mode’
LED will extinguish.
4.6 View Saved Settings– Advanced, Service and Commissioning users only.
Press the ‘MENU’ button, select ‘4 - Test Modes’ then ‘3 -View Test Settings. Use the ← →, keys to view the settings.
4.7 View Test Zones – Advanced, Service and Commissioning users only.
Press the ‘MENU’ button, select ‘4-Test Modes’ then ‘4-View Test Zones. Use the ↑ or ↓ keys to view the Zones that have been put into
Test.