EDA-Z5008 & Z5020 - Installation and Operation Manual
Electro-Detectors Page 10
3.14 Enable a Device – all access levels
To enable a previously isolated device, press ‘MENU’ and enter a valid password. Select ‘2-Disable/Enable’, select ‘2-Enable’, select ‘2-
Enable Device’. Using the or keys, select the device number to be enabled and press ‘ENTER’. To enable more devices press
‘ENTER’ or ‘CANCEL’ to exit. If all devices have been enabled ‘No Devices to enable’ will be displayed. If a previously disabled
device is enabled, and no other ‘Disablement’ conditions exist such as an isolated device/zone, then the ‘Disablements’ LED will
extinguish.
Select Device 01 Press ENTER to
enable Device 01
Use keys
3.15 Viewing Event History – all access levels
To view a log of historical system events, press ‘MENU’ followed by a valid password and select ‘3-Event Log ’. A sub menu will
appear detailing ‘VIEW EVENTS’. Select this using the cursor keys. The display will then show the most recent event. Use the up/down
keys to scroll through the recorded events. The panel stores up to 255 fire or fault events in memory. A description of the fault or fire is
recorded together with the date and time of the event. When the log becomes full the oldest entries are automatically removed to make
room for new ones. To scroll through the event log use the cursor keys.
13:24:15 01/05/11
001 CALLPOINT 06
UNIT REMOVAL
1
st
Floor Landing