Instruction manual
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 45
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
The Zerio Plus system should be maintained in accordance with the regulations and codes appropriate to the
country of installation. This schedule is based on BS5839 codes of practice.
Daily Actions
The user should check that the panel indicates normal operation. If any faults exist, they should be recorded and
the responsible person or maintenance company should be noti ed.
Weekly Actions
The user should put at least one callpoint or detector in to alarm, checking that the correct device/zone is
indicated on the panel and that the programmed sounders activate. A di erent device should be tested this way
each week. A lamps test should be carried out and any inactive LEDs reported (refer to section 8.3).
Quarterly Actions
The maintenance engineer should test at least 25% of detectors and 100% of callpoints. The devices tested should
be varied so that each device will have been tested at some point in any given 12 month period. The panel battery
connections and any relay or input connections should be checked. A visual inspection of the panel should be
carried out. Check that there are no outstanding issues in the logbook to be addressed. A lamps test should be
carried out and any inactive LEDs reported.
Annual Actions
The maintenance engineer should carry out a complete walk test. The panel battery should be tested (see
information below) and replaced if necessary. A dump of the verify table and panel table should be taken and
analysed for any change to previous records. A visual inspection of the panel should be carried out. A lamps test
should be performed and any inactive LEDs reported.
Panel Battery
Yuasa NP7-12
3-5 years expected life (20oC ambient temp)
72 hour standby
The battery may vent hydrogen while being charged. This is normal. For this reason do not install
the panel in a sealed enclosure.
The panel has been type approved using the Yuasa NP7-12 battery. Only use this battery for an
EN54 approved system.
16.0 – MAINTENANCE