Instruction manual
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 43
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
14.0 – DELAYS
It is possible to set two delays for each device or input - see 6.32 – Edit Device Options. A combined delay period of
up to 600 seconds can be applied for delay1 and delay2 (e.g. 300 seconds each).
The system will ignore any programmed delays until they are activated at Access Level 2. To turn delays on or o ,
the function key may be used, which will require an access code to be entered. Alternatively delays can be
activated with a panel input. Panel input activation must be restricted by, for example, using a keyswitch. This
function must be restricted for use by the designated person authorised to operate the panel. When turned on, the
‘Delays Active’ LED will illuminate.
At least 1 callpoint must be on the system so that a delay can be overridden. It is not possible to set a delay for a
callpoint.
14.1 – Set Function Key as a Delay Toggle Switch
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel
Options>>1.User Options
Press the key until the function key screen is displayed. Use the and
keys to select delay toggle as shown. Press the key until ‘Press
Enter to save’ is displayed and press Enter. Now when the Function key is
pressed and a correct access code is entered, the Delays Active LED will
illuminate.
14.2 – Set up a Keyswitch as a Delay Toggle Switch
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>2.Panel
Inputs>>3.Keyswitch Options
Press the key until the key function screen is displayed. Use the and
keys to select delay toggle as shown. Press the key until ‘Press Enter
to save’ is displayed and press Enter. When the key is turned, the Delays
Active LED will illuminate.
14.3 – Double Knock
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>1.User Options
This function is typically used in conjunction with delays. Upon activation of a second device the system will use
settings to signal a full evacuation. The double knock can be set to function either by a second device the same
zone, or on a system wide basis.