Instruction manual
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 38
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
10.2 - View Detailed Verify Information for a Single Device – service
and commissioning users
1.Main Menu>>5.Verify Table>>1.View Table>>2.View Detailed
From the ‘Verify Table’ menu, select ‘1-View Table’. Select ‘2View Detailed’.
Press Enter to continue. Using the and keys select number of the device
you wish to view details of and press .
Screen 1
Dev: The device number for which the information is displayed.
Count: The time in seconds since the device last transmitted.
Max: The longest interval between two successfully received
transmissions. This gives a good indication of how the
device is performing. As a device transmits every 60
seconds, if the value is around 60, it has never missed a
transmission, but if it is at 180 then two transmissions have
been missed.
RSSI: The average signal strength of the device received at the
main control panel, on a scale of -20 to +20. Any device
with a strength above 0 will normally have satisfactory
performance.
Ant: The antenna number for the signal being received.
Fail: The number of times the device has failed to transmit
within the programmed period of time.
Local: YES means the device is assigned to the selected antenna.
NO means the device is assigned to another antenna. On a
single panel, single antenna system this will always read
YES.
Last: The RSSI of the last received transmission.
Screen 2
By using the cursor key the screen opposite will appear. This screen
details the number of times the device has failed to transmit within the
time period shown. This information is for the history of the device since
the verify table or device was cleared.
View the Local Verify Information for All Devices – commissioning
users
1.Main Menu>>5.Verify Table>>1.View Table>>3.View System>>1.View Local
This will display the local information for each device. The strengths shown
are between the device and the antenna to which it is assigned.
View the Verify Information for the Whole System – commissioning
users
1.Main Menu>>5.Verify Table>>1.View Table>>3.View System>>2.View All
Allows the user to select a panel or antenna and see the count and RSSI
values for any device.