Instruction manual
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 35
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
8.3 - Lamp/Buzzer Test – advanced, service and commissioning users
1.Main Menu>>3.Test Mode>>3.Lamp/Buzzer Test
This option will illuminate all the panels LEDs in sequence, to check they are working properly. The panel buzzer
will also sound. If the buzzer does not sound, check the buzzer enable jumper link is tted on the main processor
board. See page 10 –PCB Layout. A quick lamp test can be performed from any screen by holding down the Menu
button for 2 seconds.
8.4 - Enable System Test – service and commissioning users
1.Main Menu>>3.Test Mode>>4.System Test>>1.Enable Test
If all zones are to be tested, the user can place the whole system into test mode. To comply with EN54, zones
should be tested rather than the entire system. Dependent on access level, the following options may be available:
Sounders Choose from O or On.
Tone If sounders are enabled, select a short (6 second) or full tone.
Actuators Actuators are output devices used to control equipment like magnetic doors, other alarm
systems, gas valve shut o s, air conditioning etc. It would be normal for actuators to be
disabled in an alarm test.
Beacons Choose from O or On.
Callpoint Override When set to Yes, callpoints will cause an alarm and sounders will sound if operated in test
mode. If set to No, callpoints will not cause sounders to sound if operated in test mode.
Sound Area Choose any previously set-up sound areas to activate in an alarm condition during the test.
Fire Relay Choose from O or On.
Timeout This is the amount of time before the system will automatically exit test mode operation.
Users can select a period of 1 to 48 hours. In order to comply with EN54 part 2, this
setting should not be set to anything other than ‘0’. Selecting a timeout period of ‘0’ will
keep the system in test mode inde nitely, until the test is disabled by the user.
When any zone is in test mode, the ‘Test Mode’ LED on the panel will be illuminated.
8.5 - Disable System Test – service and commissioning users
1.Main Menu>>3.Test Mode>>4.System Test>>2.Disable Test
Select this option to disable any currently active tests. The ‘Test Mode’ LED will extinguish. To comply with EN54,
zones should be tested rather than the entire system.
BS5839 and EN54 specify which tests should be performed and at what intervals. ALWAYS
FOLLOW ANY TESTING SCHEDULE OR ROUTINE RECOMMENDED BY THE SYSTEM INSTALLER. It
is recommended that the system should be tested weekly; however sounders only need to be
tested on a monthly basis. See section 16 for a suggested test schedule.