Instruction manual

INSTRUCTION MANUAL - Issue 1 - 07/2014 | 33
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
Enable a Zone – all access levels
1.Main Menu>>2.Disable/Enable>>2.Enable>>1.Zone
To enable a previously disabled zone, select it using the or keys and press Enter. To enable more zones press
Enter, or Cancel to exit. If all zones have been enabled ‘No Zones to enable will be displayed. If a disabled zone is
enabled; and no other isolated devices/zones remain, then the ‘Disablements’ LED will extinguish.
Enable a Device – all access levels
1.Main Menu>>2.Disable/Enable>>2.Enable>>2.Device
This menu allows the user to enable a previously disabled device. Using
the or keys select the device number to be enabled and press Enter. To
enable more devices, press Enter, or Cancel to exit. If all devices have been
enabled ‘No Devices to enable will be displayed. If a previously disabled
device is enabled; and no other isolated devices/zones remain, then the
‘Disablements’ LED will extinguish.
Enable Panel Input – all access levels
1.Main Menu>>2.Disable/Enable>>2.Enable>>3.Panel Input
Select this option to enable an input that has previously been disabled. Choose the input from the list and press
Enter to con rm.
Enable Sounders – all access levels
1.Main Menu>>2.Disable/Enable>>2.Enable>>4.Sounders
Select this option to enable the sounders if they have been previously disabled.
Enable Fire Routing – all access levels
1.Main Menu>>2.Disable/Enable>>2.Enable>>5.Fire Routing
Select this option to enable the  re routing relay, if it has been previously disabled.
Enable Fault Relay – all access levels
1.Main Menu>>2.Disable/Enable>>2.Enable>>6.Fault Relay
Select this option to enable the fault relay if it has been previously disabled. To comply with EN54, the fault relay
should not be disabled.
Enable Faults – commissioning users
1.Main Menu>>2.Disable/Enable>>2.Enable>>7.Faults
The enable faults list allows the user to choose which fault to enable from all the disabled faults present on the
system. To comply with EN54, faults should not be disabled.