Instruction manual
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 32
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
Disable Sounders – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>4.Sounders
The sounders can be disabled for a period of time speci ed by the user, dependent on their access level. All access
levels can disable a sounder for a period of 1 to 96 hours. A commissioning user can disable a sounder inde nitely
by selecting a time of ‘00’ hours. The sounders will ignore any re event from the panel within that time. Both the
‘Disablements’ LED and the ‘Sounder Flt/Disable’ LED will be illuminated. After the timeout period has elapsed
any disabled sounders will automatically be enabled again. When sounders are disabled, any hard wired sounder
circuits will not display short circuit and open circuit faults.
Disable Fire Routing – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>5.Fire Routing
The re routing relay can be disabled for a period of time speci ed by the user, dependent on their access level. All
access levels can disable the relay for a period of 1 to 96 hours. A commissioning user can disable the relay inde -
nitely by selecting a time of ‘00’ hours. The relay will ignore any re event from the system within that time. The
‘Disablements’ LED and the ‘Routing Flt/Disable’ LED will be illuminated. After the timeout period has elapsed, the
relay (if still disabled) will automatically be enabled again. When Fire Routing is disabled, open circuit and short
circuit faults will not be reported.
Disable Fault Relay – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>6.Fault Relay
The fault relay can be disabled for a period of time speci ed by the user, dependent on their access level. All access
levels can disable the relay for a period of 1 to 96 hours. A commissioning user can disable the relay inde nitely
by selecting a time of ‘00’ hours. The relay will ignore any fault event from the system within that time. After the
timeout period has elapsed, the relay (if still disabled) will automatically be enabled again. To comply with EN54,
the fault relay should not be disabled.
Disable Device Fault – commissioning users
1.Main Menu>>2.Disable/Enable>>1.Disable>>7.Device Fault
It is possible to disable a type of fault from a speci c device for a period of 1 to 16 weeks. Faults can be disabled
inde nitely by selecting a timeout of ‘00’ hours. First select the device number, select the fault type you wish to
disable and the timeout period. After the timeout period has elapsed, any disabled faults will automatically be
enabled again. To comply with EN54, a device fault should not be disabled.
Disable Panel Fault – commissioning users
1.Main Menu>>2.Disable/Enable>>1.Disable>>8.Panel Fault
It is possible to disable a speci c type of fault from the control panel for a period of 1 to 16 weeks. Faults can be
disabled inde nitely by selecting a timeout of ‘00’ hours. After the timeout period has elapsed, any disabled faults
will automatically be enabled again. To comply with EN54, a panel fault should not be disabled.